Load Connection - Method Iii (Series Connection) - KEPCO HSM 3.3-230 Operator's Manual

Hsm series 1000 and 1500 watt switching power supply
Table of Contents

Advertisement

2.7.5.3

LOAD CONNECTION - METHOD III (SERIES CONNECTION)

Units may be connected in series to obtain higher output voltages. Each power supply in the
series should be protected by a clamping diode connected in its non-conducting direction in par-
allel with the output; this diode protects the power supply outputs against secondary effects in
the event of a load short. (Note that this is NOT the same as the blocking diode used for parallel/
redundant operation.) Selection of the clamping diode is entirely dependent upon output volt-
age/current parameters. The clamping diode must be rated for the maximum voltage and cur-
rent of the series connection. Several clamping diodes in parallel may be required to meet the
total current rating. The user must also respect the ±500V d-c maximum isolation from output to
chassis when determining the maximum series voltage. Figure 2-5 shows a series connection
of two HSM power supplies.
FIGURE 2-5.
HSMSERIES OPR 052912

LOAD CONNECTION - METHOD III (SERIES CONNECTION)

2-9

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents