Output Status Flags; Timing Diagram For Power And Dcfail Status - KEPCO HSM 3.3-230 Operator's Manual

Hsm series 1000 and 1500 watt switching power supply
Table of Contents

Advertisement

3.14.2

OUTPUT STATUS FLAGS

The OUTPUT STATUS flags are controlled by the output fault detector circuit, which monitors
both output voltage and module current to assess d-c output status. An output fault condition is
generated if one of three fault conditions is detected: (1) Overvoltage fault, (2) Undervoltage
Fault - output voltage is outside specified regulation limits, or (3) Undercurrent fault - the power
supply module is supplying less than 70% of the current required by the circuit (as indicated by
the load sharing signal) while the output voltage is within specification limits.
A fault condition is not generated for a combination of overvoltage and undercurrent indications,
as these are mutually exclusive conditions for power supplies which are not part of a parallel-
redundantconfiguration; this combination does, however, indicate proper operation for opera-
tional power supply modules which are part of a parallel-redundant power scheme in which one
or more power supply modules are presenting overvoltage failures.
HSMSERIES OPR 052912
FIGURE 3-6.

TIMING DIAGRAM FOR POWER AND DCFAIL STATUS

3-9