Viessmann VITOTRONIC 200 Installation And Service Instructions Manual page 55

Type ho1b & mw2b, digital boiler control unit & weather-compensated, digital cascade control unit
Table of Contents

Advertisement

Vitotronic 200 and 300-K Installation and Service
"DHW" Group
(continued)
Coding in the factory set condition
67:40
With the Vitosolic:
Third set DHW temperature 104° F (40° C).
Reheating will be suppressed above the
selected temperature. The DHW tank is heated
exclusively by the solar thermal system.
68:8
With 2 DHW tank temperature sensors (code
"55:2"):
DHW tank heating stop point at set value x 0.8
69:7
With 2 DHW tank temperature sensors
(code "55:2"):
DHW tank heating start point at set value x 0.7
6A:75
Runtime, servomotor, mixing valve, heat
exchanger set, Vitotrans
222, 80 and 120 kW:
75 sec.
70:0
DHW circulation pump "ON" according to time
program when DHW heating is enabled
71:0
DHW circulation pump: "ON" according
to time program
72:0
DHW circulation pump: "ON" according
to time program
73:0
DHW circulation pump: "ON" according
to time program
75:0
DHW circulation pump "ON" during economy
mode according to time program
Possible change
67:0
Without third set DHW temperature
67:1
Input of the third set DHW temperature;
to
adjustable from 34 to 203° F (1 to 95° C)
67:95
(subject to boiler coding card of the connected
boilers)
68:2
Factor adjustable from 0.2 to 1;
to
1 step
0.1
68:10
69:1
Factor adjustable from 0.1 to 0.9;
to
1 step
0.1
69:9
6A:10
For heat exchanger set
to
Vitotrans 222, 240 kW: set 113 sec.
6A:255
Runtime adjustable from 10 to 255 sec.
70:1
DHW circulation pump "ON" according to time
program
71:1
"OFF" during DHW heating to the first set
value
71:2
"ON" during DHW heating to the first set value
72:1
"OFF" during DHW heating to the second set
value
72:2
"ON" during DHW heating to the second set
value
73:1
During time program 1x/h for 5 min. "ON"
to
to
73:6
6x/h for 5 min. "ON"
73:7
Constantly "ON"
75:1
DHW circulation pump
"OFF" during economy mode according to time
program
Code 2
55