Code 2
"General" Group
Coding in the factory set condition
82:3
Summer time starts: March
83:5
Summer time starts:
Week 5 of the selected month
84:7
Summer time starts:
Last Sunday of the selected month
85:10
Wintertime starts:
October
86:5
Wintertime starts:
Week 5 of the selected month
87:7
Wintertime starts:
Last Sunday of the selected month
88:0
Temperature unit °C
(Celsius)
89:...
Never adjust!
8A:175
Never adjust!
8F:0
All control elements active
90:128
Time constant for calculating the adjusted
outside temperature 21.3 h
91:0
Connection at terminals 1 and 2 in plug
avD disabled (external heating program
changeover)
(see page 20)
92:186
Never adjust!
Will only be displayed if "8A:176"
is programmed.
96:0
Without extension PCB for heating
circuits 2 and 3
97:2
With LON communication module:
The control unit sends the outside
temperature to the Vitotronic 200-H
98:1
Viessmann system number (in conjunction
with monitoring several systems within
one LON system with Vitocom 300)
50
(continued)
Vitotronic 200 and 300-K Installation and Service
Possible change
82:1
January to December
to
82:12
83:1
Week 1 to week 5 of the selected month
to
83:5
84:1
Monday to Sunday
to
84:7
85:1
January to December
tp
85:12
86:1
Week 1 to week 5 of the selected month
to
86:5
87:1
Monday to Sunday
to
87:7
88:1
Temperature unit °F
(Fahrenheit)
-
-
-
-
8F:1
All control elements locked out
8F:2
Only standard settings can be controlled
90:1
Fast (low values) or slow (high values) matching
to
of the supply temperature, subject to the set value
90:199
when the outside temperature changes; 1 step
10 min
91:1
Contact affects the following heating circuits:
Heating circuit A1
91:2
Heating circuit M2
91:3
Heating circuits A1 and M2
91:4
Heating circuit M3
91:5
Heating circuits A1 and M3
91:6
Heating circuits with mixing valve M2 and M3
91:7
Heating circuits A1, M2 and M3
-
-
96:1
With extension PCB for heating circuits 2 and 3
(automatic recognition)
97:0
The outside temperature of the sensor connected to
the control unit is only utilized internally
97:1
The control unit receives the outside temperature
from the Vitotronic 200-H
98:1
System number adjustable from 1 to 5
to
98:5