Viessmann VITOTRONIC 200 Installation And Service Instructions Manual page 71

Type ho1b & mw2b, digital boiler control unit & weather-compensated, digital cascade control unit
Table of Contents

Advertisement

Vitotronic 200 and 300-K Installation and Service
Fault Display Vitotronic 300-K
Fault codes
Displayed fault code
System characteristics
70
With primary store system:
Mixing valve primary circuit
"Closed"; no DHW heating
78
With primary store system:
Mixing valve primary circuit
"Closed"; no DHW heating
84
Control mode
85
Control mode
86
Control mode
87
Control mode
8C
Control mode
8D
Control mode
8E
Control mode
8F
Control mode
90
Control mode
91
Control mode
92
No solar DHW heating.
93
Control mode
(continued)
Cause
Short circuit, temperature
sensor aJB
Lead break, temperature
sensor aJB
Maintenance or error on
Vitotronic 100 of boiler 1
Maintenance or error on
Vitotronic 100 of boiler 2
Maintenance or error on
Vitotronic 100 of boiler 3
Maintenance or error on
Vitotronic 100 of boiler 4
Communication fault
Vitotronic 100 of boiler 1
Communication fault
Vitotronic 100 of boiler 2
Communication fault
Vitotronic 100 of boiler 3
Communication fault
Vitotronic 100 of boiler 4
Short circuit, temperature
sensor /, connection to
solar control module.
Short circuit, temperature
sensor aÖ, connection to
solar control module.
Short circuit, collector
temperature sensor,
connection, temperature
sensor & at solar control
module or sensor at S1 of
the Vitosolic.
Short circuit, temperature
sensor, connection at S3
of the Vitosolic.
Troubleshooting
Measures
Check temperature sensor
(see page 87) Without
temperature sensor:
Set code "4B:0"
Check temperature sensor
(see page 87)
Without temperature sensor:
Set code "4B:0"
Check maintenance display
or fault code on the
respective Vitotronic 100
Check maintenance display
or fault code on the
respective Vitotronic 100
Check maintenance display
or fault code on the
respective Vitotronic 100
Check maintenance display
or fault code on the
respective Vitotronic 100
Check and replace cascade
communication module and
connecting cable if required
Check and replace cascade
communication module and
connecting cable if required
Check and replace cascade
communication module and
connecting cable if required
Check and replace cascade
communication module and
connecting cable if required
Check temperature sensor /
(see separate installation and
service instructions).
Check temperature sensor aÖ
(see separate installation and
service instructions).
Check sensor at the solar
control unit (see separate
installation and service
instructions).
Check sensor at the solar
control unit (see separate
installation and service
instructions).
71