Viessmann VITOTRONIC 200 Installation And Service Instructions Manual page 26

Type ho1b & mw2b, digital boiler control unit & weather-compensated, digital cascade control unit
Table of Contents

Advertisement

Commissioning
Configuring a Multi Boiler System
A
Boiler number 1
Code "07:1"
(factory set condition)
With cascade
communication
module
Code "76:1"
(automatic
recognition)
Max. burner output
Set coding address
"08"
--
--
Control unit is not
fault manager
Set code "79:0"
--
--
--
--
26
B
Boiler number 2
to ...
Set code "07:2
to ..."
With cascade
communication
module
Code "76:1"
(automatic
recognition)
Max. burner output
Set coding address
"08"
--
Number of connected
boilers
Set code "35"
--
Participant no. 5
Code "77:5"
Control unit is not
Control unit is fault
fault manager
manager
Set code "79:0"
Code "79:1"
--
Control unit transmits
the time
Code "7B:1
--
Control unit transmits
outside temperature
Set code "97:2"
--
LON participant fault
monitoring
Code "9C:20"
--
Flue gas cascade
with positive pressure
Set code "7E:1"
Vitotronic 200 and 300-K Installation and Service
(continued)
C
--
--
--
Participant no. 10
Code "77:10"
Control unit is not
fault manager
Set code "79:0"
The control unit
receives the time
Set code "81:3"
Control unit
receives the outside
temperature
Set code "97:1"
LON participant fault
monitoring
Code "9C:20"
Prior to coding the Vitotronic 200, ensure the boiler is
in cascade mode. Refer to page 10.
For the Vitotronic 200, see boiler Service
Instructions
1. Press
and OK for approximately 4 seconds.
2. Use
to scroll to serviceand select with OK.
3. Use
to scroll to service functionsand select
with OK.
3. Use
to scroll to multi-boiler systemand select
with OK.
4. When complete to exit press
D
E
--
--
--
--
--
--
--
--
Participant no.
98, 99
Device is fault
manager
Device receives the
time
--
--
--
--
.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vitotronic 300-k

Table of Contents