Viessmann VITOTRONIC 200 Installation And Service Instructions Manual page 49

Type ho1b & mw2b, digital boiler control unit & weather-compensated, digital cascade control unit
Table of Contents

Advertisement

Vitotronic 200 and 300-K Installation and Service
"General" Group
Coding in the factory set condition
76:0
Without communication module
77:5
LON participant number
78:1
LON communication enabled.
79:1
With LON communication module:
Control unit is fault manager.
7A:0
Without central control of heating
circuits
Not Used
7B:1
With LON communication module:
Control unit transmits the time.
7E:0
Without flue gas cascade or with flue
gas cascade with negative pressure
(only for multi boiler systems)
7F:1
Detached house
80:6
A fault message is displayed if a fault is
active for at least 30 sec
81:1
Automatic summer/wintertime
changeover
(continued)
Possible change
76:1
With LON communication module
(automatic recognition)
77:2
LON participant number, adjustable from 1 to 99:
to
1 - 4 = Boiler
77:99
5 = Cascade
10 - 98 = Vitotronic 200-H
99 = Vitocom
Note: Allocate each number only once.
78:0
LON communication disabled.
79:0
Control unit is not fault manager
7A:1
With central control (see page 80) Heating circuit A1
7A:2
Heating circuit M2
7A:3
Heating circuit M3
7B:0
Does not transmit time
7E:1
With positive pressure flue gas cascade
7F:0
Apartment building
Separate adjustment of holiday program and time
program for DHW heating possible
80:0
Immediate fault message
80:2
The minimum fault duration before a fault message is
to
issued is adjustable from 10 to 995 sec; 1 step
80:199
81:0
Manual summer/wintertime changeover
81:2
Use of the radio clock receiver (automatic recognition)
81:3
With LON communication module:
The control unit receives the time
Code 2
5 sec
49