Basic Wiring Diagram; Main Circuit Terminals And Wiring - Fuling Inverter DZB200 Series User Manual

Dzb300 series high-performance general-purpose inverter, open-loop vector control inverter
Hide thumbs Also See for DZB200 Series:
Table of Contents

Advertisement

DZB Series

3. Basic Wiring Diagram

Users must conne ct wires according to the following circuit diagram show n below.
DC Link Reactor (option)
Use a disconnect
P1
P2
and fuse
DC+
R
R
Power source
(BR+)
3 phase
200-240V or
S
S
380-480V
50/60Hz
T
T
Multi-func tion input 1
S1
Multi-func tion input 2
S2
Multi-func tion input 3
S3
Multi-func tion input 4
S4
Multi-func tion input 5
S5
Multi-func tion input 6
S6
Digital sig nal common
DCM
(F2.01~F2.06)
EV
DC 20 V ~ 24V ( 50mA Max. )
10V
3
Frequency setting
2
0~10VDC
VI
Vr:3k~5k Ω
1
Current input
CI
VI
4~20mA
CI
ACM
shows main circuit
Fig.3-3 Basic Wiring Diagram
Note:
Breaking resistor terminals
BR+/BR-
B
raking unit and
DC Link Reactor terminals P1/P2/DC- for the inverter
B
raking unit terminals(DC+/DC-)for the inverter above
- 11-
Cha pter 3 Mechanical and Electrical Installation
No te:
DC-
U
(BR-)
M
~
Grounding
A
Multi-function indication
output contact
C
AC 250V 2A below
B
DC 30V 2A below
( F2.21)
Multi-function PHC output
48V 50mA below
(F2.19~F2.20)
FM
+
-
ACM
Analog frequency/
current meter
DC0-10V
( F2.22)
SG+
Signal+
SG-
Signal-
RS-485 Serial interface
shows control circuit
f
or the inverter of 15KW or below.
18.5KW~30KW.
37KW .
DZB Series

4. Main Circuit Terminals and Wiring

Danger
Wiring can only be done after the mains input is cut off, otherwise there will be danger of electric
shock!
O nly qualified and trained engineer can perform the wiring, otherwise there will be danger of
elect ric shock!
G rounding cable must be grounded, otherwise there will be danger of electri c shock or fire!
Danger
Please confi rm the mains volta ge level is same with that of the inverter, otherwise the inverter
may be damaged!
Make sure the ratings of the driven motor are in compliance with the inverter, otherwise the
motor may be damaged or the inverter may be in protection status!
Do not confuse the input terminals with the output terminals (U, V, W), otherwise there will be
danger of damaging the inverter!
Brake resistor cannot be conne cted between the DC bus terminals (+) and (-), otherwise fire
may occur!
1 ) Ma i n Ci r c u i t Te r mi n a l s o f I n ver t e r
Terminals
De scription
、 、
R S T ( L N)
AC input line terminals
、 、
U V W
Motor connection
B R + B R -
Connection for the br aking resistor (option)
P 1 ( D C + ) DC -
Connection for the br aking unit (option)
P 1 P 2
Connection for the
DC Link Reactor
E
G r ou nd
2 ) N ot e s o n Wi r i ng
A. Input power supply L and N or R, S and T:
There is no phase-ration requirement for the input of inverter.
B. DC bus (DC+) and (DC-) terminals:
Pay attention that the DC bus terminals (DC+) and (DC-) still have voltage after power off, and the user can
only touch the terminals after the CHARGE LED turns off and the voltage is below 36V, otherwise
there is a danger of electric shock.
When selecting the brake unit for the inverter above 18.5kW,pay attention that the polarity of (DC+) and (DC-)
cannot be reverse, otherwise the inverter may burn or be damaged. The cable length of brake unit shall
be less than 10m and twisted pair cables shall be used.
Do not connect the brake resistor directly to the DC bus, otherwise the inverter may burn or be
damaged.
- 12-
Chapter 3 Mechanical and Electric al Installation
(option)