Fuling Inverter DZB200 Series User Manual page 27

Dzb300 series high-performance general-purpose inverter, open-loop vector control inverter
Hide thumbs Also See for DZB200 Series:
Table of Contents

Advertisement

DZB Series
Func tio n
Name
Code
F2.01
S1 Terminal Function Selec tion
F2.02
S2 Terminal Function Selec tion
F2.03
S3 Terminal Function Selec tion
F2.04
S4 Terminal Function Selec tion
F2.05
S5 Terminal Function Selec tion
F2.06
S6 Terminal Function Selec tion
These parameters are used to set up the corresponding functions of digital multifunction input terminals.
setting
Function
value
Even if there is a signal input, the inverter does not run.
Terminals which a re not used can be set to be no function in
0
No Function
order to prevent malfunction
1
Forward
The inverter s forward or reverse running can be cont rol by
external terminals.
2
Reverse
By means of this t erminal the inverter s operation mode can be
three-w ire operation
defined to be three-wire control mode. For details, please refer
control
3
to the function code description of F2.07 three-wire control
mode.
4
Forward Jogging
At Jogging operat ion, the frequency and Jogging
Acceleration/Deceleration time can be found in detail
Reverse Jogging
descriptions of F4.02,F4.03 and F4.04 function codes.
5
The inverter turns off output, and the motor stop process is not
controlled by the inverter. It is often applied when the i nertia
Free-run stop
6
loading is big and there is no requirement on stop time. This
mode has the same definition as F0.19 does.
This is external failure reset. It has the same function as
Failure reset
STOP button on the keyboard. Using this function can
7
perform long-distance failure reset.
When external fault signal is input, the inverter reports it and
External fault input
8
stops.
- 47-
Chapter 6 Parameter Description
Defau lt
Setting Range
Value
0~25
1
2
0~25
0~25
4
0~25
7
0~25
12
0~25
13
Description
'
'
DZB Series
When the frequency is set by external terminal, modify the
Frequency
freque ncy up and down command. When the frequency
9
up setting
source is set as digital se tting, the set frequency can be
regulated up and down.
Frequency
10
down setting
Frequency
Using terminal can clear UP/DOWN set frequency so that set
up/down
11
freque ncy can be restored the frequency setting given by
setting clear
freque ncy command cha nnel.
8 stages speed can be set up via these 3 terminals digital
12
Multi-speed terminal 1
state combination.
13
Multi-speed terminal 2
Note: multi-speed 1 is the low position, and multi-spee d 3 is
the high position.
14
Multi-speed terminal 3
2 kinds of ACCE/DCCE time can be chosen via these two
terminals digital state combination.
ACCE/
Terminal
DCCE time
15
selection
OFF
terminal
ON
PID is temporarily out of work, and the inverter keeps its
PID control pause
16
current frequency output .
The inverter pauses at its current output frequency. After this
Traverse pause
function is cancelled, continue to start its traverse operation at
17
its current frequency.
The inverter is back to its center frequency output.
18
Traverse reset
Ensure the inverter is not interfered by external signals
Acceleration/
(excluding stop command), maintaining its current output
19
Deceleration
forbid
freque ncy.
20 25
Reserved
Reserved
Function
N ame
Code
0 two- wi re control 1
1 two- wi re control 2
Terminal control
F2.0 7
mode
2 three- wire c ontrol 1
3 three- wire c ontrol 2
- 48-
Chapter 6 Parameter Description
K1
UP terminal
DZB300
K2
DOWN
terminal
K3
UP /D OWN
c lear
DCM
termi nal
AC C/DCC time selection
Parameter
ACCE time 0
F0.08 F0.09
ACCE time 1
F4.00 F4.01
Default
Setting Range
Value
0