Chapter 6 Parameter Description - Fuling Inverter DZB200 Series User Manual

Dzb300 series high-performance general-purpose inverter, open-loop vector control inverter
Hide thumbs Also See for DZB200 Series:
Table of Contents

Advertisement

DZB Series
Function
Name
Code
3:No check N,8,2 for RTU
4:Odd check E ,8,2 for RTU
5:Even che ck O,8,2 for RTU
6:No check N,7,1 for ASCII
7:Odd check E ,7,1 for AS CII
8:Even che ck O,7,1 for ASC II
9:No check N,7,2 for ASCII
10:Odd che ck E,7,2 fo r ASCII
11:Even ch eck O,7,2 for ASCII
12:No check N ,8,1 for AS CII
13:Odd che ck E,8, 1 for ASC II
14:Even ch eck O,8,1 for ASCII
15:No check N ,8,2 for AS CII
16:Odd che ck E,8,2 fo r ASCII
17:Even ch eck O,8,2 for ASCII
Communication
F6.03
0 200 ms
response delay
Communication
0.0 in va lid
F6.04
overtime fault time
0 Alarm and free ru n sto p
1 No alarm and keep run ning
Communication
2 No alarm and stop accordin g to
F6.05
error measure
stop mode (b y communication )
3 No alarm and stop accordin g to
stop mode (b y all co ntrol mod e)
0 Response whe n write
Response
F6.06
measure
1 No respon se when wri te
- 33-
Chapter 5 Function Parameters List
Default
Modifi
Serial
Setting Range
Value
cation
No
, )
5ms
145.
),
0.1 100.0s
0.0s
146.
1
147.
0
148.
DZB Series

Chapter 6 Parameter Description

F0 Basic Function Parameters
Function
Name
Code
0 Sp eed sensorless vector
control (S VC)
F0.00
Control mode
1 V/F control
Selection of Speed Control Mode
0: Vector Control without PG: Open loop vector control
This control mode is suitable for the application requiring high torque at low speed and superior speed
control. One inverter can drive only one motor. E.g. machine tool, wiring machine, plastic injection
machine etc.
1: V/F Control Mode
V/F control mode is suitable for the application which does not require high control accuracy,
e.g. pump and fans, and also suitable for cases with one inverter driving multiple motors.
Note: If vector control mode is selected, it is a must to correctly set up the nameplate parameters
of motor, and accomplish self learning of motor parameters before operation to acquire correct
motor parameters. Only obtaining correct motor parameters can exert the high performance of
vector control mode.
Function
Name
Code
0 Ke yb oard
Comman d source
F0.0 1
1 Te rmin al
sele ction
2 Communica tion
Path Selection for the inverter Control Command
0: Keyboard Command Path
The buttons RUN and STOP on the keyboard are for operation control.
1:Terminal Command Path
Multifunction input terminals of forward, reverse, forward jogging, reverse jogging and so on,
perform the operation command control.
2:Communication Command Path
Operation command control is performed through communication pattern by upper level machine.
Function
Name
Code
0 Ke yb oard and terminal
UP/DOWN setting
Keyboard a nd terminal
1 Valid , a nd in ve rter do es not
F0.02
UP/DOWN setti ng
memorize whe n power down
2 Invalid
DZB200&300series inverter can set up the frequency though " " and " " buttons on the keyboard and
terminal UP/DOWN (Frequency setting inc rease /Frequency setting decrease), a nd as it has the highest
purvie w, it can combine with any other frequency setting path to mainly accompl ishes the fine adjustment
of inverter output freque ncy during control system commissioning.
- 34-
Chapter 6 Parameter Description
Default
Setting Range
Value
1
Default
Setting Range
Value
0
Default
Setting Range
Value
0