Fuling Inverter DZB200 Series User Manual page 26

Dzb300 series high-performance general-purpose inverter, open-loop vector control inverter
Hide thumbs Also See for DZB200 Series:
Table of Contents

Advertisement

DZB Series
Func tio n
Name
Cod e
Upper torque l imit setting
0.0
200.0%(inverter rated current)
F1.1 9
The setting 100.0% is corresponding to the rated output current.
The function code below F1.20~F1.24
a re valid to V/F control ( F 0.00 1 ), but invalid to vector
control.
Functio n
Name
Cod e
0 Linear V/F curve
V/F curve setting
F1.2 0
1 square torque V/F curve
0: Linear V/F c urve. It is applicable to constant torque load.
1: 2.0 exponential V/F curve. It is applicable to variable torque load, such as blower, pump e tc.
Output Voltage (V)
V
b
Linear V/F curve
2.0 exponential
V/F curve
/ 1
f 3
b
Fig. 6-6 V/F curvediagram
Func tio n
Name
Cod e
F1.21
Torque boost
0.0% (auto)
0.0% 50.0% (relative to motor
F1.2 2
Torque boost cut-off
rated frequency)
Torque Boost is mainly applied to less than cut-off frequency (F1.22). The V/F curve after boost is
shown in following figure. Torque booth can improve the low frequency torque performance of V/F control.
Based on the load, a torque should be chosen properly. For heavy loa d, increase the tor que boost, but
the torque boost should not be set too big, which will result in the motor operating at overexcitation and
that it could be overheated, and also the inverter output current is big, reducing efficiency.
When the torque boost is set as 0.0%, the inverter is at automatic torque boost.
Torque boost cut-off frequency: below this frequency, torque boost is valid, and above this frequency
setting, torque boost is invalid.
- 45-
Chapter 6 Parameter Description
Default
Setting Range
Value
15 0.0%
Default
Setting Range
Value
0
f
Output Frequency f
b
Default
Setting Range
Value
%~
0
0.1
30.0
20 .0%
DZB Series
Output Voltage (V)
V
b
V
b o o st
Fig. 6-7 Manual torque boost diagram
Function
N ame
Code
F1.23
V/F sli p compensation limit 0.0 200.0%
Setting this parameter can compensate the motor speed change produced because of undertaking
loading while on V/F control, to increase the rigidity of motor mechanical performance. This value
should be set as the motor rated slip frequency.
Function
Name
Code
0:No Oper ati on
Energy Conservation
F1.24
Sele ction
1:Energy Conservation
When the motor is running in no-load or lower-load during,the inverter can
by
automatically current kf the load。
Note:This function is especially valid for variable torque load (such as fan and pump).
F2 Input and Output Terminal Function Parame ters
Function
N ame
Code
On-off signal filter times
F2.00
1 10
It sets up S1-S6, VI and CI terminal s sample filtering time. In big interference situation, this parame ter
should be increased in order to prevent maloperation.
- 46-
Chapter 6 Parameter Description
f
f
Output Frequency f
c u t -o f f
b
Default
Setting Range
Value
100%
Default
Setting Range
Value
0
adjust
output voltage
Default
Setting Range
Value
5