DZB Series
This parameter defines four different control modes which controls the inverter operation through
external terminals.
0: Two-wire type control, integrate Enable with direction. This mode is the most often used two-wire
control mode. The motor forward and reverse operations are determined by the defined FWD and REV
terminal command.
K1
FWD
DZB
K2
Series
REV
DCM
Fig. 6-8 Two-wire operation mode 1
1: Two-wire control, separate Enable from direction. When this mode is used, the defined FWD is enable
terminal. The direction is determined by the defined REV state.
K1
FWD
DZB
K2
Series
REV
DCM
Fig. 6-9 Two-wire operation mode 2
2: Three-wire control 1, integrate Enable with direction. At this mode, EN is the Enable terminal with the
direction controlled by the defined FWD. REV define the direction.
SW1
FWD
SW2
EN
DZB
K
Series
REV
DCM
Fig. 6-10 Three-wire operation mode 1
K FWD/REV switch
SW1 RUN button
EN is defining the corresponding terminal function as Function 3
- 49-
Chapter 6 Parameter Description
Operation
K1
K2
Command
OFF
STOP
OFF
ON
OFF
FWD
OFF
ON
REV
ON
ON
STOP
Operation
K1
K2
Command
OFF
OFF
STOP
ON
OFF
FWD
OFF
ON
STOP
ON
ON
REV
Operation
K
C ommand
OFF
FWD
ON
REV
SW2 STOP button
"
"
Three-wire operation control .
DZB Series
3: Three-wire control, separate Enable from direction. At this mode EN is the Enable terminal, SW1 or
SW2 define operating command and control direction at the same time. Stop command is defined by SW2.
SW1
FWD
SW2
EN
K
REV
COM
Fig. 6-11 Three-wire operation mode 2
S W1 FWD opera ting button
SW2 STOP button
EN is def ining the corresponding terminal function as Function 3
Note: For two-wire operation mode, when FWD/REV terminal is enabled and the stop command
produced by other sources stops the equipment, the inverter does not start to operate after the stop
command disappears even if the control terminal FWD/REV is still valid. If the inverter needs to
operate , it is required to trigger FWD/REV again.
Function
N ame
Code
UP/DOWN frequency
F2.0 8
0.0 1 5 0.00 Hz/s
increment variable rate
Terminal UP/DOWN regulates the change rate of frequency setting.
Function
N ame
Code
F2.09
VI lower limit
0.0 0V 10 .00V
VI lower limit
-100.0% 100.0%
F2.10
corresponding setting
F2.11
VI upper limit
0.0 0V 10 .00V
VI upper limit
F2.12
-100.0% 100.0%
corresponding setting
VI input filtering time
F2.13
0.0 0s 10 .00s
- 50-
Chapter 6 Parameter Description
DZB
Series
K REV operating button
"
"
Three-wire operation control .
Default
Setting Range
Value
0.50Hz /s
Default
Setting Range
Value
0.0 0V
0.0%
10.00V
100.0%
0.1 0s