Advertisement

DZB Series
) 、 (
):
C.Brake resistor terminals of BR+
BR-
The brake resistor terminal is effective only for the inverte r of 15kW or below and has a built-in brake
unit. Select the recommended resistor w ith the cable length of less than 5m, otherwise the inverter may
burn or be damaged.
D. Inverter output U, V and W:
Inverter output terminals cannot connect to capacitors or surge snub devices, otherwise the inverter may
be in protective status or damaged.
If the cables between the motor and the inverter are too long, electrical resona nce may occur due to the
distributed capacitance, which may result in damaging the motor insulation or big leakage current, so if
the cable length is longer than 100m, AC reactor must be installed.
E. Grounding Terminal
:
Grounding Terminal must be connected to earth reliably and the grounding resistance shall be less than
Ω
5 , otherwise the equipment may work abnormally or be damaged. Do not sha re the PE and neutral line
of the mains supply.
5. Control Terminals and Wiring
1 Layout of Control Terminals(Fig.3-4,Fig3-5)
Ⅰ   Ⅰ  
F M A C M M O
A
B
C
10V
V
C
 
 
S1
S2 D C M
S3
S4
S5
S6
D C M
S1 S2 DCM S3 S4
S5
S6 DCM
EV MO1MCM 10V VI
2 Function of Control Terminals
Terminal
Function
Multi-function PHC output 1
MO -MCM
1
Multi-function PHC output 2
MO -MCM
2
Multi-function indication output co ntact
A-B
Multi-function indication output co ntact
B-C
A1-B1
Multi-function indication output co ntact
Multi-function input 1
S1-DCM
Multi-function input 2
S2-DCM
Multi-function input 3
S3-DCM
Multi-function input 4
S4-DCM
Multi-function input 5
S5-DCM
S6-DCM
Multi-function input 6
Auxiliary control power source
EV-DCM
Analog voltage input
VI-ACM
CI-ACM
Analog current input
Analog frequency/current meter
FM-ACM
SG+,SG-
Serial communication interface
Power supply for speed setting
10V~ACM
- 13-
Cha pter 3 Mechanical and Electrical Installation
M O
M C M
1
2
EV
SG + SG -
CI FM ACM SG+ SG-
A1
B1
A
B
C
Refer toF2.19 F2.21
Refer to F2.00 F2.06
DC 24V (50mA Max.)
0~10 V (Max. output freq.) Input
4~20 mA (Max. output freq.) Input
0 ~10 V (Max. output freq.) Output
Refer to F2. 22
RS-485 serial port
+10 V (20 mA max. output current)
DZB Series
3 ) N ote s o n C on t rol Te r m in al s:
A) Analog input terminal:
Since the weak analog voltage signal is easily disturbed by external disturbance source, shielded cable
shal l be used and the c able shall be as short as possible and the length shall not exceed 20m, as shown in
the figure 3-6:
Less than 20m
Potentionmeter
Fig. 3 -6 Analog Input Terminal of DZB Serie s Inverter
If the analog signal is severely disturbed, filter capacitor or ferrite core shall be installed
at the analog signal source as show n in the Fig. 3-7:
Wind 2 - 3 turns
C
External analog source
Ferrite core
0.022 uF 50V
Fig. 3 -7 Analog Input Terminal With Filter devices
B) Digital input termi nal:
The inverter judges the ON/OFF status of these terminal s by receiving the digital signal. Hence, all the
external contactors are those with high reliability of weak signal conduction.
If the open collector is employed to provide ON/OFF signal for the inverte r digital input terminal, then
it shall be considered that there is error operation caused by power supply interference.
It is recommended to use contact control mode.
C) Digital Output terminal:
When digital output terminal drives a relay, the coil of the relay shall be installed a snubbing diode,
othe rwise the DC 24V power supply may be damaged.
- 14-
Chapter 3 Mechanical and Electric al Installation
+10V
DZB
VI
ACM
VI
DZB
ACM