Installing the VentiMatic Shutter
Assembly
The AAF
-HermanNelson
VentiMatic Shutter Assembly is a one-way
®
®
shutter. It is a continuously variable, gravity-actuated, room exhaust
vent that operates in direct response to positive static pressure, opposing
any airflow into the room resulting in a slight positive pressure.
The VentiMatic Shutter Assembly is mounted on an installed wall louver.
For larger units with 100% ventilation air dampers, two VentiMatic
Shutters may be mounted side by side on the same louver. See figure 27.
The size and appearance of the wall louvers with or without optional
grilles used with the unit ventilator, and the VentiMatic Shutter, are
identical.
When installing VentiMatic Shutter(s) on the wall louver, make sure
all moving parts are free to operate unobstructed and placed level
and plumb for proper operation. If optional steel interior wall grille is
furnished, install as shown in Figure 25.
Figure 25: Louver , VentiMatic Shutter, Interior Wall Grille
Details, Dimensions
As Directed
By Architect
7"
(178mm)
Bird
Not
Screen
Less
Than 9"
(229mm)
Cement Mortar
Do Not Block Drain
Holes With Caulk or
Mortar
Notes:
1. Horizontal blade wall louver shown. Vertical blade wall louver also
available with Ventimatic shutter.
2. Optional exterior grille matches unit ventilator wall louver in material
and design. Mounted on wall louvers.
3. Optional steel interior wall grille should be used to conceal the
interior wall opening whenever the Ventimatic shutter is not located
behind shelf cabinets. Hardware to mount the interior wall grille is
not included.
CAUTION
For proper operation, the VentiMatic shutter assembly must
be mounted on the same wall as the unit ventilator louvers to
neutralize wind effect.
Table 4: Recommended Wall Openings For Wall Louvers
Recommended
Wall Openings
B
C
For Wall Louvers
Length
Height 24" Shutter 36" Shutter
48"
51"
48
"
10
"
5
7
8
8
(1219) (1295) (1222)
(267)
60"
63"
60
"
10
"
5
7
8
8
(1524) (1600) (1527)
(267)
72"
75"
72
"
19
"
5
7
8
8
(1829) (1905) (1832)
(495)
Page 14 of 42
Cement Mortar
" (19mm) Approx.
3
4
Steel Interior Wall Grille
(Optional) See Note 3
C
see table 4
12
"
5
8
(314mm)
3
" (19mm) Approx.
4
Maximum Number of
VentiMatic
VentiMatic Shutters
Shutter(s)
Which Can Be Mounted Air Capacity
On Standard Louver
Maximum
cfm
2
0
1000
1
1
1250
0
2
1500
Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ
Figure 26: Single VentiMatic Shutter & Wall Louver
Outside
10
"
3
8
(264mm)
Decorative Exterior Grille Also Available (See Note 2, above)
Figure 27: Two VentiMatic Shutters & Wall Louver
Aluminum Wall Louver
Assembly with Bird Screen
(See Note 1)
Outside
10
"
3
8
(264mm)
Figure 28: Louver, VentiMatic Shutter, Interior Wall Grille
Details, Dimensions
As Directed
By Architect
Bird
Screen
Do Not Block Drain Holes
With Caulk or Mortar
Note:
1. Horizontal blade wall louver shown. Vertical blade wall louver
L/s
also available.
2. The optional exterior grille shown mounted on the wall louver.
472
3. The optional steel interior wall grille is used to conceal the
590
interior wall opening whenever the Ventimatic shutter is not
located behind shelf cabinets. Hardware to mount the interior
708
wall grille is not included.
Aluminum Wall Louver
3" (76mm)
Assembly With Bird Screen
(See Note 1)
4
"
1
8
(105mm)
B
see table 4
23
" (606mm)
7
8
or
35
7
" (911mm)
8
2" (51mm)
(Bird Screen not shown)
B
see table 4
Decorative Exterior Grille Also Available (See Note 2)
(Bird Screen not shown)
Cement Mortar
7"
(178mm)
3/4" (19mm) Approx.
Steel Interior Wall Grille
(Optional) See Note 3
Not
Less
Than 9"
(229mm)
12⅝"
(314mm)
3/4" (19mm) Approx.
Cement Mortar
Steel
VentiMatic
Shutter
Assembly
3'' (76mm)
VentiMatic
Shutter
Assembly
Center Cover
C
see table 4
IM 1083

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

GrqErq

Table of Contents