Electrical Data
Table 13: Model ARQ, ERQ, GRQ Electrical Data – Size 048
Voltage Range
Voltage
Min.
Max.
208/60/1
197
228
230/60/1
207
253
208/60/3
197
228
230/60/3
207
253
460/60/3
414
506
Notes:
Electric Heat Options are with Compressor
1
FLA = Full Load Amps
LRA = Locked Rotor Amps
IM 1083
Compressor
Room
Fan
RLA
LRA
FLA
2.7
23.6
96.0
2.7
23.6
96.0
2.7
15.0
88.0
2.7
15.0
88.0
2.7
7.1
41.0
RLA = Rated Load Amps
Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ
Heating Options
Auxiliary Heat Type
Refrigerant Heating
Low (3-elem.)
Electric Heat
1
High (6-elem.)
Refrigerant Heating
Low (3-elem.)
Electric Heat
1
High (6-elem.)
Refrigerant Heating
Low (3-elem.)
Electric Heat
1
High (6-elem.)
Refrigerant Heating
Low (3-elem.)
Electric Heat
1
High (6-elem.)
Refrigerant Heating
Low (3-elem.)
Electric Heat
1
High (6-elem.)
Power Supply
Heater
Heater
MCA
kW
Amps
32.2
12.0
57.7
104.3
24.0
115.4
176.4
32.2
11.6
50.0
94.7
23.0
100.0
157.2
21.5
12.0
33.3
63.1
24.0
66.6
104.7
21.5
11.5
28.9
57.5
23.0
57.7
93.6
11.6
11.5
14.4
29.6
23.0
28.9
47.7
MCA = Minimum Circuit Ampacity
Page 29 of 42
Maximum
Fuse
50
110
200
50
100
175
35
70
110
35
70
100
15
30
50