Daikin ARQ Installation Manual page 31

Self-contained water source heat pump unit ventilator
Table of Contents

Advertisement

Figure 51: 4-pin Plug MicroTech II Control Wiring Diagram
Communication
Module
Note:
The N2 Bus can use either solid or stranded wires of the following types:
3-wire twisted cable, 2 twisted-pair telephone cable, or two twisted pair
with shield. The wiring is polarity sensitive.
The polarity of the signal must always be maintained throughout the
network. Always connect + to + and - to -. The shield connection must
be continuous throughout the entire network and must be connected to
earth ground at one (and only one) point.
Use Belden 8471, NEMA Level 4, or Echelon-approved equivalent wire.
Since the L
W
communication wiring is polarity insensitive, no polarity
ON
ORKS
must be observed when making connections via the unshielded twisted-pair wiring.
Wiring: Use twisted shielded pair (Connect Air W221P-2544 or equivalent).
Daisy-chain and tie shield to earth ground at one point only.
The polarity of the signal must always be maintained throughout the network.
Always connect + to + and - to -. The shield connection must be continuous
throughout the entire network and must be connected to earth ground
at one (and only one) point.
Figure 52: 10-pin Plug MicroTech II™ Wiring Diagram
P6 (10-pin)
Connector
Unit Ventilator
Comm
xBO-1
BO-6
BO-6
Comm
24vac Supply
24vac Comm
Note: Not all external input options are available for all models.
Figure 53: 12-pin Plug MicroTech II™ Control Wiring Diagram
P1 (12-pin)
Connector
Unit Ventilator
GND
AI-2
Comm
AI-1
LED
GND
Comm
BI-6
BI-5
BI-4
Note: Not all external input options are available for all models.
IM 1083
(4-pin)
Male Connector
(4-pin)
Unit Ventilator
Female Connector
Red
1
Black
2
3
GND
P6 (10-pin)
Connector
Wire
Caps
601
601A
602
602A
603
603A
604
604A
605
605A
606
606A
608
608A
610
610A
P1 (12-pin)
Connector
Wire
Caps
896
896
GRN
GRN
BLK
BLK
WHT
WHT
RED
RED
896
896
908
908A
907
907A
906
906A
905
905A
Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ
Optional Building Automation System (BAS)
BACnet
®
RT+
FTT–10 (B)
RT-
FTT–10 (A)
GND
(By others)
Shield
External Output
Option 1 Device
(by others)
Lights On/Of f f
Signal or
Motorized Water
Valve Open/Close
Remote Wall Sensor
(Option)
1
5
Shield
6
Setpnt Adjst.
4
Comm
3
Sensor
2
LED
Shield
External Input
External Input
Option 2 Device
Option 3 Device
(by others)
Ventilation Lockou t
(default) or
Exhaust Interlock
L
W
Metasys
®
ON
ORKS
N2+
N2–
(By others)
(By others)
External Output
External Output
Option 2 Device
Option 3 Device
(by others)
(by others)
Fault Indication
Auxiliary Heat
or
Signal
or
Pump Restart
Exhaust Fan
Signal
On/Off Signal
External Input
Option 1 Device
(by others)
(by others)
Unoccupied (default)
Remote
or Dewpoint Humidity
Shutdown
®
GND
Page 31 of 42