Outdoor Unit Parts Replacement - Toshiba RAS-B10N3KV2-E Service Manual

Split type air conditioner
Hide thumbs Also See for RAS-B10N3KV2-E:
Table of Contents

Advertisement

12-3. Outdoor Unit
No.
Part name

Common
1. Detachment
procedure
2. Attachment
Procedure
NOTE
Wear gloves for this job.
Otherwise, you may injure your
hands on the parts, etc.
1) Stop operation of the air conditioner,
and turn off the main switch of the
breaker for air conditioner.
2) Remove the valve cover.
(ST1TØ4 × 10L 3 pcs.)
• After removing screw, remove the
valve cover pulling it downward.
3) Remove cord clamp (ST2TØ4 × 14L
3 pcs.), and then remove connecting
cable.
4) Remove the upper cabinet.
(ST1TØ4 × 10L 5 pcs.)
• After removing screws, remove the
upper cabinet pulling it upward.
1) Attach the water-proof cover.
NOTE
The water-proof cover must be
attached without fail in order to
prevent rain water, etc. from entering
inside the indoor unit.
2) Attach the upper cabinet.
(ST1TØ4 × 10L 5 pcs.)
3) Perform cabling of connecting cable,
and attach the cord clamp.
• Fix the cord clamp by tightening
the screws (ST2T∅ 4 x 14L 3 pcs.),
fitting 2 concave parts of the cord
clamp to each connecting cables.
4) Attach the valve cover.
(ST1T∅ 4 x 10L 3 pcs.)
Insert the upper part into the square
hole of the side cabinet, set hook
claws of the valve cover to square
holes (at three positions) of the main
unit, and attach it pushing upward,
This line shall
be pavallel to
the front cabinet
How to mount the water-proof cover
91
FILE NO. SVM-12050
Remarks
Upper cabinet
Waterproof cover
Valve cover
These 2 bending
parts shall be
put inside of a unit
by bending
these 2 ports.
This part shall be
put on
the side cabinet.
Fit the corner of
the water
proof cover to
the corner of
the front cabinet.
This part shall cover the
gap between the inverter
box and the front cabinet.