Item
2. Indoor fan
<In cooling operation>
motor control
(This operation controls the fan speed at indoor unit side.)
The indoor fan (cross flow fan) is operated by the phase-
control induction motor. The fan rotates in 5 stages in
MANUAL mode, and in 5 stages in AUTO mode, respec-
tively. (Table 1)
COOL ON
Fan speed setup
AUTO
Ta
[ ˚C ]
+2.5
a
+2.0
b
+1.5
c
+1.0
d
+0.5
e
Tsc
(Table 1) Indoor fan air flow rate
Fan speed
level
COOL HEAT DRY
WF
WE
WD
WC
WB
WA
W9
W8
W7
W6
W5
W4
W3
W2
W1
Operation flow and applicable data, etc.
MANUAL
Indication
L
L+
M
M+
H
Air volume AUTO
M+(WB)
*3
*3 : Fan speed = (M + –L) x 3/4 + L
*4
*4 : Fan speed = (M + –L) x 2/4 + L
*5
*5 : Fan speed = (M + –L) x 1/4 + L
(Linear approximation
L(W6)
from M+ and L)
RAS-B10N3KV2-E
Fan speed
(rpm)
UH
1210
H
1210
UH
UH
M+
1170
H
H
1120
M
M+
M+
1040
M
1000
M
L+
960
L
870
L+
L-
L+
850
L
L
760
L-
UL
L-
760
UL
UL
700
SUL
SUL
650
SUL
500
500
(Fig. 1)
Fan speed
W6
(L + M) / 2
W9
(M + H) / 2
WC
(Fig. 2)
RAS-B13N3KV2-E
Air flow rate
Fan speed
Air flow rate
(m3/h)
(rpm)
(m3/h)
571
1300
620
571
1300
620
546
1250
590
515
1200
570
465
1080
490
440
1050
465
415
990
434
359
870
359
347
860
353
291
770
297
291
770
297
253
720
266
222
670
234
129
520
141
129
500
129
28
FILE NO. SVM-12050
Description
* Symbols
UH
: Ultra High
H
: High
M+
: Medium+
M
: Medium
L+
: Low+
L
: Low
L-
: Low–
UL
: Ultra Low
SUL
: Super Ultra Low
* The fan speed broadly varies due
to position of the louver, etc.
The described value indicates one
under condition of inclining
downward blowing.
1) When setting the fan speed to L,
L+, M, M+ or H on the remote
controller, the operation is
performed with the constant
speed shown in Fig. 1.
2) When setting the fan speed to
AUTO on the remote controller,
revolution of the fan motor is
controlled to the fan speed level
shown in Fig. 2 and Table 1
according to the setup tempera-
ture, room temperature, and heat
exchanger temperature.