Wiring Failure (Interconnecting And Serial Signal Wire); Outdoor Unit Does Not Operate; Outdoor Unit Stops In A Little While After Operation Started - Toshiba RAS-B10N3KV2-E Service Manual

Split type air conditioner
Hide thumbs Also See for RAS-B10N3KV2-E:
Table of Contents

Advertisement

11-5-2. Wiring Failure (Interconnecting and Serial Signal Wire)

(1) Outdoor unit does not operate

1) Is the voltage between
Confirm that transmission from indoor unit to outdoor unit is correctly performed based upon the follow-
ing diagram.
NOTE:
• Measurement should be performed 2 minutes and 30 seconds after starting of the operation.
• Be sure to prepare a diode for judgment.
Terminal block at indoor side
Red
White
Normal time
: Voltage swings between DC15 and 60V. ...................Inverter Assembly check (11-7-1.)
Abnormal time : Voltage does not vary.

(2) Outdoor unit stops in a little while after operation started

<Check procedure> Select phenomena described below.
1) The outdoor unit stops 10 to 20 minutes after operation started, and 10 minutes or more are required to
restart the unit.
Gas circulation amount is down.
Measure gas pressure.
Thermo. operation of compressor
2) If the unit stops once, it does not operate until the power will be turned on again.
To item of Outdoor unit does not operate.
3) The outdoor unit stops 10 minutes to 1 hour after operation started, and an alarm is displayed.
(Discharge temp. error check code 03, 1E Sensor temp. error check code 02, 1C)
Gas leak
P.M.V. is defective.
Miswiring of connecting wires of indoor/outdoor units
Clogging of pipe and coming-off of TC sensor
R
S
and
of the indoor terminal block varied?
3
S5277G
2
1
Terminal block
S5277G or equivalent (G or J type)
(Diode with rated voltage of 400V
or more is acceptable.)
Tester
Gas shortage
Gas leak
Pipe clogging
Refer to the chart in 11-6.
74
FILE NO. SVM-12050

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ras-10n3av2-eRas-b13n3kv2-eRas-13n3av2-e

Table of Contents