11-6. How to Check Simple the Main Parts

<Check procedure>
Gas leakage,
disconnection of TS/TC
sensors (Check code 02, 1C)
Is coil of the pulse motor valve
Is connecter of coil connected to inverter?
Is positioning sound of valve (sound hitting to stopper) heard
from valve when the air conditioner starts the operation after turning off power
of the air conditioner once?
Are temp. sensors of indoor/outdoor units correctly set to the holder?
NOTE :
The temperature sensors which are used to control pulse motor valve
include indoor heat exchanger sensor (TC), outdoor heat exchanger temp.
sensor (TE), outdoor suction temp. sensor (TS) and outdoor sensor (TO).
Gas amount check and valve clogging check
Remove TC sensor connector from the P.C. board in indoor unit.
(Remove connector from the P.C. board.)
Operate the air conditioner in COOL mode by TEMP button
("Beep" sound is heard if keeping pushed for 10 seconds.).
The operation enters temporary operation mode which fixes opening degree of compressor speed.
Check condensation at outlet of PMV, and then check operating pressure from the service port.
Existence of condensation at outlet of P.M.V.
If there is condensation at outlet (1/4 inch=Ø6.35mm valve side),
Check the operating pressure from service port, and add gas if pressure is low.
1C
Valve drive check
(P.M.V.) correctly set?
YES
YES
YES
YES
the valve is clogged.
1E
Discharge temp. error,
gas leakage
(Check code 03, 1E)
NO
NO
NO
NO
YES
75
FILE NO. SVM-12050
Set it correctly.
Set it correctly.
Replace coil valve.
Set it correctly.
Replace valve.
Add gas.