Name

Service level

P01
Control sequence
P02
User operating mode profile (mode button)
P03
User fan mode selection
P04
Selection of °C or °F
P05
Sensor calibration (intern, extern)
P06
Standard temperature display
P07
Display info line
(2nd line of LCD)
P08
Comfort setpoint
P09
Minimum setpoint in Comfort mode
P10
Maximum setpoint in Comfort mode
P11
Energy Saving heating setpoint
P12
Energy Saving cooling setpoint
P13
Electric reheater in cooling mode
P14
Button lock function
Note
46 / 60
Siemens
Building Technologies
Tel: 01823 665660
Heronhill - for all your Siemens requirements
4.15.1 Service level
Factory setting
When 2-pipe /
2-stage:
1 = Cooling only
When 4-pipe:
4 = H and C
1
0
0 (°C)
0 K
0
0
21 °C
5 °C
35 °C
15 °C
30 °C
ON
0
Parameter available
Parameter not available
Parameter display depends on selected application and function
RDG100.../RDG110.../RDG140.../RDG160... Basic Documentation
Functions
www.heronhill.co.uk
Range
0 = Heating only
1 = Cooling only
2 = H/C changeover manual
3 = H/C changeover auto
4 = Heating and Cooling
1 = (Auto) - Comfort - Protection
2 = (Auto) - Comfort - E Saving - Prot
0 = Auto - Manual
1 = Manual
2 = Auto - Manual - Prot
0 = Degrees Celsius (°C)
1 = Degrees Fahrenheit (°F)
– 3 ... 3 K
0 = Room Temperature
1 = Setpoint
0 = --- (No display)
1 = °C and °F
5 ... 40 °C
5 ... 40 °C
5 ... 40 °C
OFF, 5 ... WcoolE-saving;
(WcoolE-saving = 40 °C max)
OFF, WHeatE-saving ... 40 °C;
(WHeatE-saving = 5 °C min)
ON: Enabled
OFF: Disabled
0 = Unlocked
1 = Auto locked
2 = Manual locked
0..1
0..1
0..1
0..1
CE1P3076.en