Siemens RDG100 Documentation page 48

Room thermostats with display, for fan coil units
Hide thumbs Also See for RDG100:
Table of Contents

Advertisement

P52
Fan operation
P53
Fan speed
P54
Fan overrun time
(only when electr. heater is used)
P55
Switching point fan speed high
P55
ECM fan max. output
P56
Switching point fan speed med
P56
ECM fan min. output
P57
Switching point fan speed low
P57
ECM: Switching point fan
P58
Fan start booster
P59
Fan minimum on time (dwell time)
P60
Fan kick in Comfort (time until next kick)
P61
Fan kick in E-saving mode (time until next kick)
P62
Clean filter reminder run-time
P65
Protection heating setpoint
P66
Protection cooling setpoint
P67
Fan start delay in 2P control
P68
Prolong Comfort period
P69
Temporary setpoint Comfort
(see also Comfort setpoint P08)
P70
Infrared receiver
P71
Reload factory settings
Name
Diagnostics & test
d01
Application type
d02
X1 status
d03
X2 status
d04
D1 status
d05
Test mode for checking the Y1/Y2
actuator direction
(press left button to escape)
d06
Test mode for checking the Y3/Y4
actuator direction
(press left button to escape)
48 / 60
Siemens
Building Technologies
Tel: 01823 665660
Heronhill - for all your Siemens requirements
1
3-speed
60 sec
100%
ECM: 80%
65%
ECM: 30%
10%
ECM:10%
ON
2 min
0
OFF
Off (0)
8 °C
OFF
0 s
OFF
OFF
ON
OFF
Factory setting
Diagnostics
Diagnostics
Diagnostics
Diagnostics
---
---
Parameter available
Parameter not available
RDG100.../RDG110.../RDG140.../RDG160... Basic Documentation
Functions
www.heronhill.co.uk
0 = Disabled
1 = Enabled
2 = Heating only
3 = Cooling only
1 = 1-speed
2 = 3-speed
0 ... 360 sec
80..100%
ECM: fan min....100%
30..75%
ECM: 0%...fan max.
1..15%
ECM: 0..100%
ON: enabled
OFF: disabled
1 ... 6 min
0...89 min, OFF(90 min)
0...359 min, OFF(360 min )
Off, 100 ... 9900 hours
OFF, 5 ... W Cool Prot;
(W Cool Prot = 40 °C max)
OFF, W Heat Prot ... 40;
(W Heat Prot = 5 °C min.)
0.. 180 s
OFF; 15 ... 360 min
OFF = Disabled
ON = Enable
OFF = Disabled
ON = Enabled
OFF = Disabled
ON = Reload start
Range
0 = (No application)
1 = 2-pipe
2 = 2-pipe with electric heater
3 = 2-pipe with radiator
4 = 4-pipe
5 = 2 stage heat or cool
6 = 4-pipe with electric heater
0 = Not activated (for DI)
1 = activated (DI)
0...49 °C = cur. temp. value (for AI)
00
= HC input short
100
= HC input open
0 = Not activated (for DI)
1 = activated (DI)
0...49 °C = cur. temp. value (for AI)
00
= HC input short
100
= HC input open
0 = Not activated (for DI)
1 = activated (DI)
00
= HC input short
100
= HC input open
"---" = no signal on outputs Y1 and Y2
OPE = output Y1 forced open
CLO = output Y2 forced closing
"---" = no signal on outputs Y3 and Y4
OPE = output Y3 forced open
CLO = output Y4 forced closing
CE1P3076.en
28 May 2009