Control sequences

4.7.1
Sequences overview (setting via parameter P01)
The sequence can be set via parameter P01.
The thermostats can be used in systems featuring:
• Heating only (P01=0)
• Cooling only (P01=1)
• Manual heating / cooling changeover (P01=2)
• Automatic heating / cooling changeover (P01=3)
• Heating and cooling mode (e.g. 4-pipe system) (P01=4)
The available modes depend on the application (selected via DIP switch, see
section 4.5).
P01 = 0
P01 = 1
T °C
Cooling mode
1) Chilled / heated ceiling and radiator applications, see section 4.7.9
2) Manual and automatic changeover for 4-pipe applications, see section 4.7.6:
– 4-pipe manual changeover (P01=2) means activating either cooling or
heating outputs
– 4-pipe automatic changeover (P01=3) means swapping the control outputs
according to a heating / cooling sensor or remote switch (main and secondary
application), see section 4.7.6
RDG100.../RDG110.../RDG140.../RDG160... Basic Documentation
Functions
www.heronhill.co.uk
P01 = 2
T °C
T °C
Manually select
Automatic
heating or
heating/cooling
cooling mode
changeover via
external water
temperature
sensor or
remote switch
2)
P01 = 3
P01 = 4
T
T °C
Heating and
cooling mode,
i.e. 4-pipe
2)
CE1P3076.en