Room Temperature Setpoints - Siemens RDG100 Documentation

Room thermostats with display, for fan coil units
Hide thumbs Also See for RDG100:
Table of Contents

Advertisement

Comfort mode
Setpoint limitation
P09 < P10
P09 ≥ P10
Examples
P09 < P10
P09 ≥ P10
Temporary setpoint
Energy Saving mode
Protection mode
Caution
12 / 60
Siemens
Building Technologies
Tel: 01823 665660
Heronhill - for all your Siemens requirements
4.3

Room temperature setpoints

The setpoint in Comfort mode can be adjusted via the rotary knob.
For energy saving purposes, the setpoint setting range can be limited to minimum
(P09) and maximum (P10).
• If the minimum limit P09 is set lower than the maximum limit P10, both heating
and cooling are adjustable between these 2 limits
• For heating or cooling applications (e.g. 2-stage):
– The setting range in cooling mode is from P09...40 °C in place of 5...40 °C
– The setting range in heating mode is from 5...P10 °C in place of 5...40 °C
• For heating and cooling applications (e.g. 4-pipe):
– P09 is the setpoint for cooling and P10 the setpoint for heating
– The setpoint can no longer be adjusted via the rotary knob
2-pipe heating OR cooling
5°C
18°C
25°C
P09
P10
Cooling setpoint adjustable 18...25 °C
Heating setpoint adjustable 18...25 °C
5°C
21°C
25°C
P10
P09
Cooling setpoint adjustable 25...40 °C
Heating setpoint adjustable 5...21 °C
If the "Temporary setpoint function" is enabled via parameter P69, the setpoint
adjusted via the rotary knob is set back to the Comfort basic setpoint when the
operating mode changes.
The factory setting for the Comfort basic setpoint is 21 °C and can be changed via
parameter P08.
Use control parameters P11 and P12 to adjust the Energy Saving mode setpoints.
The heating setpoint is factory-set to 15 °C, and the cooling setpoint to 30 °C.
Use control parameters P65 and P66 to adjust the Protection mode setpoints.
The heating setpoint is factory-set to 8 °C (frost protection) and to OFF for cooling.
If a setpoint is set to OFF (P65, P66), the thermostat does not maintain the setpoint
in the corresponding mode (heating or cooling).
This means no protective heating or cooling function and thus risk of frost in the
heating mode or risk of overtemperature in cooling mode!
RDG100.../RDG110.../RDG140.../RDG160... Basic Documentation
Functions
www.heronhill.co.uk
4-pipe heating AND cooling
40°C
5°C
18°C
P09
Cooling setpoint adjustable 18...25 °C
Heating setpoint adjustable 18...25 °C
Cooling fixed = 25 °C (P09)
Heating fixed = 21 °C (P10)
40°C
Fax: 01823 665807
25°C
40°C
P10
CE1P3076.en