1)
Heat pump application covered by RDG110
(SPDT = relay with NO and NC contact)
2)
With ECM fan control DC 0...10 V
Key
Y1
Heating or heating/cooling valve actuator
Y2
Cooling valve actuator
E1
Electrical heater
Note
The diagrams above only show the water-based fan coil applications, but not the compressor
Universal applications
Automatic heating /
cooling changeover
Remote heating /
cooling changeover
External / return air
temperature sensor
16 / 60
Siemens
Building Technologies
Tel: 01823 665660
Heronhill - for all your Siemens requirements
The RDG1xx.. can also be used on universal applications, e.g. fan coil-based
cooling and floor heating, or chilled ceiling and electrical heater, etc.
For more detailed information, refer to subsection 4.7.9 ff.
4.6

Additional features

The water temperature acquired by the changeover sensor (QAH11.1 + ARG86.3)
is used to change over from heating to cooling mode and vice versa. When the
water temperature is above 28 °C (parameter P37), the thermostat changes over to
heating mode, and to cooling mode when below 16 °C (parameter P36).
If the water temperature is between the 2 changeover points immediately after
power-up, the thermostat starts in heating mode.
The water temperature is acquired at 30-second intervals and the operating state is
updated accordingly.
M
T
w
16
28
M Operating mode
T
Water temperature
w
The QAH11.1 cable temperature sensor for automatic heating / cooling changeover
can be replaced by an external switch for manual, remote changeover:
X2
M
QAH11.1
T °C
The sensor or switch can be connected to input terminal X2 (factory setting) or X1
or D1 (switch only), depending on the commissioning of the inputs (P38, P40, P42).
See also section 4.10 "Multifunctional input".
The thermostat acquires the room temperature via built-in sensor, external room
temperature sensor (QAA32), or external return air temperature sensor (QAH11.1)
connected to multifunctional input X1 or X2.
Inputs X1 or X2 must be commissioned accordingly. See section 4.10 "Multi-
functional input".
RDG100.../RDG110.../RDG140.../RDG160... Basic Documentation
Functions
www.heronhill.co.uk
M1 1-speed or 3-speed fan
B1 Return air temperature sensor or external
room temperature sensor (optional)
B2 Changeover sensor (optional)
[°C]
Cooling mode
Heating mode
X2
Contact open
T
M
Contact closed
3076Z03
heating mode
cooling mode
CE1P3076.en