Installing The Floor-Mounting Brackets; Figure 2-4 Adjusting The Leveling Pads On The Stabilizer Leg - Sun Microsystems StorEdge 6920 System Getting Started Manual

Installing and configuring the system
Hide thumbs Also See for StorEdge 6920 System:
Table of Contents

Advertisement

5. Use the leveling wrench to adjust the feet on both stabilizer legs so that they
touch the floor (
FIGURE 2-4
Adjusting the Leveling Pads on the Stabilizer Leg
FIGURE 2-4
6. Slide both stabilizer legs under the system cabinet.
7. Resecure the leveling wrench inside the system cabinet.
8. Close the back door.

Installing the Floor-Mounting Brackets

Skip this section if you have installed the stabilizer legs and adjusted the leveling
pads.
Use the four floor-mounting brackets to attach the system to the floor. The bolts to
secure the floor-mounting brackets are not included.
Caution – Do not bolt the floor-mounting brackets to the deck plating of a raised
(computer-room) floor, because this would result in an unstable mount.
Note – If you are installing the floor-mounting brackets over previously installed
threaded rods, loosely attach the floor-mounting brackets to the rods and then to the
system.
).
Chapter 2 Installing the System
17