Summary of Contents for Sun Microsystems StorEdge 6120
Page 1
Sun StorEdge 6120 Array Site Preparation Guide Sun Microsystems, Inc. 4150 Network Circle Santa Clara, CA 95054 U.S.A. 650-960-1300 Part No. 817-0960-10 April 2003, Revision A Submit comments about this document at: http://www.sun.com/hwdocs/feedback...
Page 2
Copyright 2003 Sun Microsystems, Inc., 4150 Network Circle, Santa Clara, California 95054, Etats-Unis. Tous droits réservés. Sun Microsystems, Inc. a les droits de propriété intellectuels relatants à la technologie incorporée dans le produit qui est décrit dans ce document. En particulier, et sans la limitation, ces droits de propriété intellectuels peuvent inclure un ou plus des brevets américains énumérés à...
The Sun StorEdge 6120 array is a high-performance, modular, scalable storage device that contains an internal RAID controller and up to 14 disk drives with Fibre Channel connectivity to the data host. In a Sun StorEdge 6120 HA array configuration, two array controller units are paired using interconnect cables for back-end data and administrative connections.
Page 6
Rack-Ready Sun StorEdge 6120 Array FIGURE 1 For a detailed product overview and installation instructions, refer to the following Sun StorEdge 6120 array documents available at the Sun documentation web site: http://www.sun.com/documentation Sun StorEdge 6120 Array Documentation TABLE 1 Application...
Safety Information Install Sun StorEdge 6120 arrays in accordance with the local safety codes and regulations at the facility site. Make sure you read and follow the safety precautions in the Sun StorEdge 6120 Array Regulatory and Safety Compliance Manual before installing an array configuration.
This section describes facilities environmental requirements for the Sun StorEdge 6120 array, and includes the following sections: “Environmental Specifications” on page 5 “Electrical and Power Specifications” on page 5 “Physical Specifications” on page 6 Sun StorEdge 6120 Array Site Preparation Guide • April 2003...
X, Y, Z) Electrical and Power Specifications All Sun StorEdge 6120 arrays require two independent power sources. Each array cabinet has two power conditioners (distribution), for redundancy, mounted in the base of the cabinet. Each array has two power and cooling units, and each power and cooling unit on the array connects to a different conditioner.
(+/-) 5%. The customer facilities must provide suitable surge protection. Physical Specifications The section contains the physical requirements for Sun StorEdge 6120 arrays. Physical Dimensions Array and Cabinet Physical Specifications TABLE 4...
Cabling Specifications and Requirements Cable Specifications TABLE-6 Cable Type Connector Maximum Length Host interface (FC-AL) LC-SFF LC-SFF 82.021 ft (25 m) to LC fiber-optic cable Shielded Ethernet: RJ-45 328.084 ft (100 m) 10/100BASE-T, category 5 Serial (Available only to qualified RJ-45 82.021 ft (25 m) field service representatives.)
Page 12
Sun StorEdge 6120 Array Site Preparation Guide • April 2003...
Need help?
Do you have a question about the StorEdge 6120 and is the answer not in the manual?
Questions and answers