Rack-Mounting the Sun StorEdge 5210
NAS/Expansion Unit
Rack-mounting the Sun StorEdge 5210 NAS and expansion unit(s) consists of the
following procedures:
Determining the position of the Sun StorEdge 5210 NAS and expansion unit(s) in
the rack.
Mounting the outer slide rail assemblies onto the rack.
Sliding the rails on the chassis into the slide assemblies.
Attaching the Sun StorEdge 5210 NAS and/or expansion unit(s) to the rack.
Before you begin rack-mounting the Sun StorEdge 5210 NAS or expansion unit(s):
Check that the maximum ambient operating temperature in the rack does not
exceed 95° F (35° C).
Pick a location that allows unrestricted air flow for the cooling fans.
Make sure mounting the units into the rack will not tip the rack over, even when
the Sun StorEdge 5210 NAS and expansion unit(s) are fully extended from the
rack.
Install the components so that the rack is stable. Begin loading from the bottom of
the rack to the top.
Caution – Uneven loading of the rack can cause dangerous instability.
Make sure the power outlets are close enough to the Sun StorEdge 5210 NAS and
expansion unit(s) for the power cords to reach the cabinet properly and supply
power to the Sun StorEdge 5210 NAS and expansion unit(s).
Make sure the power cables are properly grounded.
Grounding Procedure
You must maintain reliable grounding of this equipment. The Sun StorEdge 5210
NAS system (including head and expansion units) must be connected to a dedicated
20A receptacle.
Caution – The Sun StorEdge 5210 NAS server and expansion units contain several
components sensitive to static-electrical discharge. Surges of static electricity (caused
by shuffling your feet across a floor and touching a metallic surface, for example)
Chapter 2 Installing the Sun StorEdge 5210 NAS
13