Eclipse Winnox WX Series Installation Manual page 22

Hide thumbs Also See for Winnox WX Series:
Table of Contents

Advertisement

tep 6: Verify ettings
Tap "C"
Figure 4.10 Verify pressure settings
etting verification:
ith burner lit, drive control motor to high fire.
.
ai t for the chamber to reach normal operating conditions
.
(e.g. chamber temperature, process flows, etc.).
easure high fire fuel using fuel flow measurement
.
device. Compare this to rated high fire on Data Sheet.
easure high fire air differential pressure between tap
.
(C) and the chamber. Compare this pressure to the “ Air
P vs. Input” chart on the data sheet.
rive the control motor to low fire and verify low fire
.
flame signal and flame appearance (if viewing).
Chamber
ycle burner from high to low several times to check
.
repeatability of settings.
eadjust burner if the settings do not repeat as excepted. If
.
necessary, refer to Chapter 5, Maintenance & Troubleshooting.
se the system setup summary sheet on page 30 to record
.
all setup data as an aid for future troubleshooting and setup
operations.
Do not turn the combustion air blower off until the chamber
temperature is below 250°F (121° ). This will prevent hot
gases from back flowing into the burner and blower causing
damage to the burner.
.
top the burner.
clipse Winnox WX Series v1, Installation Guide No. 111, 8/26/05