Eclipse Winnox WX Series Installation Manual page 18

Hide thumbs Also See for Winnox WX Series:
Table of Contents

Advertisement

tep 3: Ignite the Burner
Low fire start
arning:
These procedures are written with the assumption the burner has a flame
monitoring control system installed and operating. A proper purge cycle must be
part of the system and purge timing should not be bypassed.
8
Tap "E"
Low fi r e start :
3
1.
rive control motor to low fire.
2.
Be sure combustion air blower is running.
3.
Turn bias adjusting screw
3.
complete (360°) turns counter-clockwise (up) from bottom.
4.
Open main gas manual shut off valves.
With pressure taps open, connect manometer between tap “E” and the
5.
chamber .
6
Set system control to stay at low fire during and after ignition sequence.
7.
. Attempt to ignite burner.
During trial for ignition, adjust bypass pressure regulator
limiting orifice
to achieve the appropriate
chamber as listed in the appropriate data sheet.
ote:
If viewing the flame, it should be blue with flashes of yellow. The flame should be
completely within the combustion tube. When firing propane or butane, a proper
low fire flame may have sustained flashes of yellow.
.
f burner does not ignite:
ttempt to ignite burner again to purge air from the gas piping.
f burner still does not ignite, turn bias adjusting screw
clockwise to increase gas flow.
epeat until burner ignites. If necessary, refer to Chapter 5,
.
Maintenance and Troubleshooting in this manual, for help.
fter ignition, verify low fire flame:
hut off gas. When chamber temperature is below 250°F (121°C),
shut off combustion air blower.
estart combustion air blower and ignite burner.
easure low fire gas pressure to the burner gas inlet
.
at
is within the range specified on the Data Sheet for your burner.
erify repeatability of ignition and low fire flame signal.
.
lose all pressure taps.
0.
clipse Winnox WX Series v1, Installation Guide No. 111, 8/26/05
Figure 4.5 Low fire start
1
Main gas
shut-off
valvetrain
4
2
on ratio regulator spring column three
P between tap “E” and the
nd djust ble
a half turn
V erify pressure

Advertisement

Table of Contents
loading