6 Electrical Connection
6.4.2 Assembling the DC Connectors
Figure 12: DC connectors
Position
A
B
Cable requirements:
☐ PV1-F cable must be available.
☐ External diameter of the cable: 5 mm ... 8 mm
☐ Conductor cross-section: 2.5 mm² ... 6 mm²
Proceed as follows to assemble each DC connector.
1. Strip 12 mm of the cable insulation.
2. Lead the stripped cable all the way into the
DC connector. Ensure that the stripped cable and
the DC connector have the same polarity.
40
STP5-9TL-IA-en-10
Description
Negative DC connector
Positive DC connector
SMA Solar Technology AG
+
Installation Manual