Night Mode (Silent Mode) Schedule - Mitsubishi Electric GB-24A Operation Manual

Air-conditioner control system centralized controller
Hide thumbs Also See for GB-24A:
Table of Contents

Advertisement

6-2 Night Mode (Silent Mode) Schedule

Click on [Function2]-[Night Mode Schedule] in the menu to open the night mode (silent mode) schedule screen
and make necessary settings to switch the outdoor unit operation mode to the night mode (low-sound
operation), and set the night mode time interval.
Use this mode when low-sound operation of the outdoor unit is preferable during night.
Note: Make this setting only when all the units operate normally. When connection error occurs at the indoor or the outdoor unit,
night mode target units may not be displayed normally.
Depending on the type of outdoor units connected, this function may not be available.
Note: The noise level to be reduced varies depending on the unit model.
Note: If the user logs in as a manager, the operations may be prohibited.
Night mode start time
Click to set the start time.
Target outdoor units
Click to select the outdoor
unit, which performs night
mode control.
Refresh
Read setting data from
GB-24A.
(1) Set the time interval in [Night mode start time] and [Night mode end time].
Note: When the starting time and the ending time is the same, night mode operation will always be performed.
(2) Select the outdoor unit, which performs night mode operation from [Target outdoor units].
Note: M-NET address numbers for each outdoor unit are displayed in the target unit field.
(3) Click [Save Settings] to send setting data to the GB-24A.
27
Night mode end time
Click to set the end time
Save settings
Send setting data to
GB-24A.