Recommended Mounting Heights - Re-Verber-Ray LD Series Installation Manual

Ld series infrared tube heater
Table of Contents

Advertisement

LD
Series
Chart 3.1 •
Recommended Mounting Heights and Coverages
NOTE: This chart is provided as a guideline. Actual conditions may dictate variation from this data.
10 ft.
25,000
30,000
40,000
15 ft.
40,000
50,000
20 ft.
40,000
50,000
30 ft.
50,000
Factory recommended mounting heights are listed as a guideline. If infrared heaters are mounted to low
or to high, they may result in discomfort or lack of heat. Detroit Radiant Products Company generally
recommends observing the recommended mounting heights to optimize comfort conditions. However,
certain applications such as spot heating, freeze protection, outdoor patio heating or very high ceilings
may result in the heaters being mounted outside of the factory recommended mounting heights.
* Optional protective guard (P/N: PG) is required when mounting below 8-ft.
Figure 3.3
Mounting Height Dimensions • see chart 3.1 for dimensions
Dimension B
Distance between
heater rows
Dimension C
Maximum distance between heater and wall
Note: Dimensions A, B & C are based upon heaters hung at the factory recommended mounting height.
8' - 11'
20' x 12'
8' - 11'
20' x 12'
10' - 14'
20' x 12'
8' - 13'
20' x 12'
10' - 15'
22' x 15'
8' - 13'
20' x 13'
9' - 15'
22' x 15'
9' - 14'
22' x 15'
Dimension A
Dimension A
3.0
Installation • Recommended Mounting Heights
N/A
10' - 20'
N/A
10' - 20'
N/A
10' - 20'
N/A
10' - 20'
N/A
20' - 30'
12' x 12'
10' - 20'
12' x 12'
20' - 30'
15' x 15'
20' - 30'
11
20' - 40'
16'
20' - 40'
16'
20' - 40'
16'
20' - 40'
16'
30' - 50'
18'
20' - 40'
16'
30' - 50'
18'
30' - 50'
18'
Dimension C
Maximum
distance
between
heater
and wall

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ld-10-40Ld-15-40Ld-15-50Ld-20-40Ld-20-50Ld-30-50

Table of Contents