Lockout:
The controls will automatically lockout the heater system when an external or system fault occurs. There
are two types of lockout:
Soft Lockout: The heater will attempt to light three times. In the event of a failed attempt to light, (gas
pressure, valve, no flame sense etc.), the heater will enter a soft lockout period for 30
minutes and then attempt to light three more times before entering hard lockout mode.
Hard Lockout: If proof of flame is not established, a component failure occurs or blockages are evident,
the heater will enter hard lockout. If lockout occurs, the control can be reset by briefly
interrupting the power source. Refer to Chart 4.1 below for a description of LED codes.
Externally located operational indicator lights are provided to assist in troubleshooting of the heater. Refer
to pages 40-43 for additional troubleshooting.
Figure 4.1
Operational Indicator Lights
Chart 4.1
LED Fault Code Status
LED CODE
Initial Flash on power up, then
steady off
Steady on
1 flash
2 flashes
3 flashes
4 flashes
No flash on 117V start-up
*Some LED codes have a time delay before the LED will flash.
Light 3 (red)
Light 1(amber)
Indicates Diagnostic
Fault Code Status
(see Chart 4.1)
Operational Indicator Lights
FAULT STATUS
Normal operation
Module failure/Internal fault
Ignition failure
APS 1 failure
APS 2 failure
Solenoid valve fault/Leaky valve/
Flame amplifier fault
Transformer fault
39
4.0
Operation
Light 2 (amber)
Indicates High
Indicates Low
Fire Mode
Fire Mode
FAULT CODE DELAY*
Diagnostics
Immediate
Immediate
32 minutes
12 minutes
22 minutes
Immediate
Immediate