Rack-Mounted Installation

Installation Guidelines

Juniper Networks recommends that you use a standard EIA distribution
rack. Refer to
Equipment Rack Requirements
Guidelines and
Requirements, for detailed rack information.
Before installing the systems in a rack, consider the following guidelines
and refer to
Figure
4-2:
You can install up to three ERX-14xx models, six ERX-7xx models, or
fourteen ERX-310 routers in a single 7-ft. (2.1 m) rack.
Installing multiple systems in a single rack allows you to maximize
your available space.
You can install an ERX-14xx model, an ERX-7xx model, and an
ERX-310 router together in the same rack (see
If you install an ERX-7xx model or ERX-310 router directly above an
ERX-14xx model in the same rack, you must install a plenum between
the ERX-7xx model or ERX-310 router and the ERX-14xx model so
that the air can circulate between the systems (see
plenum is available from Juniper Networks.
If you install an ERX-14xx model above an ERX-7xx model or
ERX-310 router, there is no need to install a plenum between the units
because the ERX-7xx models and ERX-310 routers vent air out the
side of the chassis.
Warning: To maintain airflow requirements, a plenum must be installed above
an ERX-14xx model before any other piece of equipment is installed above the
router.
Install heavier systems, such as an ERX-14xx model, on the bottom of
the rack. Lighter systems, such as the ERX-310 router, should be
mounted higher in the rack.
Rack-Mounted Installation
E-Series Routers
in
Chapter 3, Installation
Figure
4-2).
Figure
3-2). This
4-3