PROMPTS
Supervision
16
(24 Hours)_
Old Alarm Time
17
(10 Minutes)_
GSM Flt Time
18
(60 mins)_
Flt Rel ON Y/N
19
(N)_
Pwr Loss Rpt Y/N
20
(Y)_
Low Bat Rpt Y/N
21
(Y)_
Tamper Rpt Y/N
22
(Y)_
WWW.DIYALARMFORUM.COM
4204/
ZONE
ENTRY
2-4204
TRIG.
WWW.DIYALARMFORUM.COM
Section 3: Programming the 7845GSM
OPTIONS
• 30 Day
The AlarmNet network must hear at least one
supervisory message from the module during this
• 24 Hrs
supervision period; otherwise, AlarmNet notifies
• None
the central station that a communication failure
has occurred. (If the supervision period is changed
after registration, you must re-register the
module.)
Press the [space] key to scroll through choices.
UL NOTE: Must be set to 24 hours.
• 10 Min
Sets how long an undeliverable alarm is retried for
• 15 Min
delivery to the central station. If the message is not
• 30 Min
validated, it is retried until the old alarm time is
• 1 Hr
reached or the message is validated.
• 2 Hrs
Press the [space] key to scroll through choices.
• 4 Hrs
• 8 Hrs
• 12 Hrs
UL NOTE: Must be set to 10 minutes.
• 24 Hrs
In the event the module detects a communication
[01-99]
path failure, enter the time delay (in minutes)
[00] = not
before the module notifies the control panel with a
used
trouble message (and trips the Fault Output if
used (terminal 11); see next question). The control
panel can then notify the central station.
UL NOTE: Must be two (02) minutes.
If enabled, the fault open collector output is
[Y], [N]
normally energized to ground, and de-energizes
(open circuit) in the event of a module fault. For
conditions that trip the fault relay refer to Module
Supervision Features in Section 1.
Set to [Y] if fail-safe mode is desired.
See Wiring for Module Fault Relay in Section 2.
UL NOTE: Must be set to "Y".
Sends a primary power loss report to the central
[Y], [N]
station within 1-3 hours after its detection. A
restore report is sent within 1-3 hours after power
is restored.
UL NOTE: Must be set to "Y."
[Y], [N]
Sends a low-battery report when a low battery
condition exists. A low-battery restore is
automatically sent when the low battery condition
clears.
UL NOTE: Must be set to "Y" unless used with
LynxR-I series controls. Must be set to "N" when
using LynxR-I series controls.
[Y], [N]
Sends a tamper report when the module detects a
tamper condition. A tamper restore is
automatically sent when the tamper condition
clears.
UL NOTE: Must be set to "Y."