Honeywell AlarmNet 7845GSM Installation And Setup Manual page 19

Digital cellular communicator
Hide thumbs Also See for AlarmNet 7845GSM:
Table of Contents

Advertisement

PROMPTS
Enable DW Y/N
18
(N)_
Direct Wire Addr
19
(28)_
Supervision
20
(24 Hours)_
Old Alarm Time
21
(10 Minutes)_
GSM Flt Time
22
(60 mins)_
Flt Rel ON Y/N
23
(N)_
Pwr Loss Rpt Y/N
24
(Y)_
WWW.DIYALARMFORUM.COM
ENTRY
OPTIONS
[Y], [N]
[01-30]
• 30 Day
• 24 Hour
• None
•10 Minutes
• 15 Minutes
• 30 Minutes
• 1 Hour
• 2 Hours
• 4 Hours
• 8 Hours
• 12 Hours
• 24 Hours
[01-99]
[00] = not used
[Y], [N]
[Y], [N]
WWW.DIYALARMFORUM.COM
Section 3: Programming the 7845GSM
DESCRIPTION
Applies only to VISTA-128BP/250BP and FBP Series
controls.
Enables Direct Wire Downloading over GSM.
If [N], skip to Prompt 20: "Supervision."
When using Direct Wire downloading, the 7845GSM
communicates with the panel as an alpha keypad to
initiate the direct wire download session. Enter the
appropriate device address.
NOTES:
1. This address must also be programmed as an
alpha keypad in the control panel (Device
Programming Mode). DO NOT connect an actual
keypad (or any other device) assigned to this
address.
2. This address must be unique from the "Device
Address" entered in Prompt 17.
The AlarmNet network must hear at least one
supervisory message from the module during this
supervision period; otherwise, AlarmNet notifies the
central station that a communication failure has
occurred. (If the supervision period is changed after
registration, you must re-register the module.)
Press the [space] key to scroll through choices.
The old alarm time sets how long an undeliverable
alarm is retried for delivery to the central station. If
the message is not validated, it is retried until the old
alarm time is reached or the message is validated.
Press the [space] key to scroll through choices.
In the event the module detects a communication path
failure, enter the time delay (in minutes) before the
module notifies the control panel with a trouble
message (and trips the Fault Output if used; (terminal
11) see next prompt). The control panel can then notify
the central station.
UL NOTE: Must be two (02) minutes.
If enabled, the fault open collector output is normally
energized to ground, and de-energizes (open circuit) in
the event of a module fault. For conditions that trip the
fault relay refer to Module Supervision Features in
Section 1.
Set to [Y] if fail-safe mode is desired.
See Wiring for Module Fault Relay in Section 2.
UL NOTE: Must be set to "Y."
Sends a primary power loss report to the central
station within 1-3 hours after its detection. A restore
report is sent within 1-3 hours after power is restored.
UL NOTE: Must be set to "Y."
3-5