XI581/2 BUSWIDE OPERATOR INTERFACE
Auto Sign-Off

Alarm Information

Select Alarms from Main Menu
Select Alarm Information Option
Main Menu
Password
Time Programmes
Data Points
If you are signed on to the XI581/2 and do not press any keys for 10 minutes, the
operator terminal automatically signs you off.
This section describes how to view alarm information from the local controller as
well as buswide alarms. For buswide alarms, the section describes how to set the
buswide alarm mode and acknowledge the buswide alarm flag.
Purpose
To view selected alarm information, including the last 99 alarms, the controller has
generated and stored in memory, all current alarms (critical and non-critical), current
critical alarms, current non-critical alarms, and buswide alarms. All operators can
perform this task.
1. At the Main Menu, use the arrow keys to move to and highlight the Alarms
option. Press Enter (↵) to complete the selection.
RESULT: The 'View Alarms' screen displays options for viewing alarm
2. Use the arrow keys to move to and highlight the desired option:
CONTROLLER_01
Running
15.12.1994
Alarms
Trend Buffer
System Clock
System Data
information.
View Alarms
Alarm Buffer
All Points in Alarm
Critical Points in Alarm
Non Critical Points in Alarm
Buswide Alarms
Table 5. Alarm Buffer Options and Alarm Type Options