XI581/2 BUSWIDE OPERATOR INTERFACE
Access Level
Select Data Points from Main Menu
Select Hours Run Option
5. Press the plus or minus keys to change operating mode to AUTO. Then press
Enter (↵) to complete the change.
RESULT: The entry in the Operating Mode field stops blinking but is still
6. Use the arrow keys to move to and highlight Back. Then press Enter (↵) to
complete the selection.
RESULT: The 'Data Points' screen redisplays.
Purpose
To display accumulated runtime information (in hours).
You must have access level 3 to perform this task.
1. At the Main Menu, use the arrow keys to move to and highlight Data Points.
Press Enter (↵) to complete the selection.
RESULT: The 'Data Points' screen appears. User Address is highlighted by
Data Points
User Address
Manual Operation
Accumul. Runtime
Type Selection
Points in Trend
2. Use the arrow keys to move to and highlight Accumul. Runtime. Press Enter
(↵) to complete the selection.
RESULT: The display window lists the points and the number of hours each has
Accumulated Runtime
Supply fan
Exhaust fan
Burner
Htg. zone pump
Cafe. hood
NOTE:
3. Press Cancel (C) to return to the list of point description options. When you are
finished, repeatedly press Cancel (C) to return to the Main Menu.
Trend log memory collects and saves up to 200 of the most recent change-of-state
(COS) conditions from up to 20 trend points in a controller. A trend point is a point
that is designated (in the controller's application program) to report changes in its
state/value to the trend log memory.
Operators can request a trend log report which extracts the trend point COS
information from the trend log memory and outputs the trend information in the
XI581/2 display window.
This function disables a point so it cannot contribute associated COS activity to the
trend log memory and it cannot appear in a trend log report output.
NOTE: To enable a point's trending capability, see section "Selecting Points by
User Address" (page 53).
highlighted.
default.
Suppress Alarm
Add Template
Delete Template
Modify Template
Template Search
run since it was last serviced.
The hours run for all points may not be able to appear in the display
window at the same time.
57
ALPHABETIC REFERENCE
Listing Accumulated Runtime
1267 L L L L
1257 I
476 1
736 I
123 M
Disabling a Point from Trend Log
EN2B-0126 (74-3554-8)