Buswide operator interface
Table of Contents

Advertisement

ALPHABETIC REFERENCE
Select the Switch Point
Modify the Switch Point
EN2B-0126 (74-3554-8)
Time
Time of day when the change in state or value should occur.
Time is in 24-hour (HH.MM) notation where HH=00-23 and
MM=00-59. For example, enter the time you want the
temperature in the conference room to change.
Value
If the selected point is an analog point, enter the new value
that the controller should execute (for example, the new set
point temperature for the conference room). If the selected
point is a digital point, enter the new state (for example, OFF,
ON, or AUTO).
Opt.
If the DDC program uses this point for optimization, select ON
to enable optimization or OFF to disable optimization.
— Use the arrow keys to move to and highlight a field and press Enter (↵) to
complete the selection. The first digit you can input begins to blink.
— Press the plus and minus keys to increment and decrement the value of the
digit.
— Press the right arrow key to move to the next digit within the field.
— Repeat this input procedure until the entire field is correct. Then press Enter
(↵) to complete the field entry. The cursor highlights the field you just
modified.
8.
To create additional switch point fields, repeat previous process.
RESULT: The new switch point becomes part of the selected daily program for
the selected point.
9.
Press Cancel (C) to return to the list of time programs.
Continued from the "Switch Points" section.
Time
Progr.: Time Program 1
Daily Progr.: Weekday
Address: C1_DO_1
Time
: 08:00
Value
: On
Next
Previous
New
5. If the switch point in the window is not the one you want to modify, use the arrow
keys to move to and highlight Next or Previous and press Enter (↵) to display
other switch points.
6. You can modify information in the following fields:
Time
Time of day when the change in state or value should occur.
Time is in 24-hour (HH.MM) notation where HH=00-23 and
MM=00-59. For example, enter the time you want the tem-
perature in the conference room to change.
Value/Status
If the selected point is an analog point, enter the new value
that the controller should execute (for example, the new set
point temperature for the conference room). If the selected
point is a digital point, enter the new state (for example, OFF,
ON, or AUTO).
— Use the arrow keys to move to and highlight a field and press Enter (↵) to
complete the selection. The first digit you can input begins to blink.
— Press the plus and minus keys to increment and decrement the value of the
digit.
— Press the right arrow key to move to the next digit within the field.
— Repeat this input procedure until the entire field is correct. Then press Enter
(↵) to complete the field entry. The cursor highlights the field you just
modified.
84
XI581/2 BUSWIDE OPERATOR INTERFACE
Opt.: OFF
Delete
Back
Modify Switch Point