Commissioning
PV Overvoltage
NOTICE!
Excessive DC voltage can destroy the Sunny Mini Central!
Immediately disconnect the Sunny Mini Central!
1. Switch the line circuit breaker off.
2. Remove the Electronic Solar Switch.
3. Disconnect the DC plug connectors.
Check DC voltage!
• Higher than 700 V: Contact the planner / installer of the PV generator for assistance.
• Lower than 700 V: Connect the Sunny Mini Central to the PV generator again as described in
section 5.3 „PV Generator (DC) Connection" (26).
If the message reappears, disconnect the Sunny Mini Central again and contact SMA
(see section 12 „Contact" (62)).
6.1.1 Setting the Display Language
You can set the language of the display using the switches on the underside of the display assemblies
inside the Sunny Mini Central.
Proceed as follows:
1. Open the Sunny Mini Central as described in section 7.1 „Opening the Sunny Mini Central"
(46).
2. Set the switches for the required language, as shown below.
Language
Switch S2
German
B
English
B
French
A
Spanish
A
3. Close the Sunny Mini Central as described in section 7.2 „Closing the Sunny Mini Central"
(48).
42
SMC6-8TL-IEN093231
Switch S1
B
A
B
A
SMA Solar Technology AG