Security
The following is not permitted:
• Using the Sunny Mini Central for purposes other than those indicated in this installation guide,
• Connecting other power supply units other than PV modules to the Sunny Mini Central,
• Modifying the Sunny Mini Central or installing components that have not been expressly
recommended or sold by SMA Solar Technology!
2.2 Safety Instructions
DANGER!
Danger to life due to high voltages in the Sunny Mini Central!
All work on the Sunny Mini Central must be carried out by a qualified electrician.
CAUTION!
Danger of burn injuries due to hot housing parts!
• Do not touch the housing body during operation.
• Only touch the cover during operation.
NOTICE!
Dust or water entering the Sunny Mini Central can damage the device!
If the Electronic Solar Switch has been pulled out, the Sunny Mini Central only has a
protection rating of IP21.
If the device has been temporarily decommissioned, proceed as follows to restore the IP65
protection rating:
• Unplug all DC plug connectors and seal them with the protecting caps provided.
• Attach the Electronic Solar Switch.
PV generator ground connection
Comply with the local requirements for grounding the modules and the PV generator.
SMA Solar Technology recommends connecting the generator frame and other electricity
conducting surfaces such that there is continuous conduction and to connect them to the
ground in order to reach maximum protection for property and persons.