Technical data (cont´d)
Ethernet Adapter
SPA-ZC402 dimensions and weight
ETHERNET ADAPTER
190
EXTERNAL
POWER
175
U
aux
L
N
+
Fig. 3
SPA-ZC 402 dimensions
Type
SPA-ZC 402
Tests and conditions
Environmental tests and conditions
Recommended service temperature range
Limit temperature range (short-term)
Transport and storage temperature range
Dry heat test
Dry cold test
Damp heat test

Electromagnetic compatibility tests

EMC immunity test level meets the requirements listed below
1 MHz burst disturbance test, class III
Common mode
Differential mode
Electrostatic discharge test, class IV
For contact discharge
For air discharge
115
SPA-ZC 402
PLASTIC
GLASS
IEC 61850
MODBUS / TCP
SPA / TCP
24-60 VDC
110-220 VDC, 100-240 VAC
POWER
LINK
TX
LAN
RX
DIAG
TX
RX
ETHERNET
Use M5 mounting screws
Dimensions [mm]
190 x 115 x 35
-10...+55°C (continuous)
-40...+70°C
-40...+85°C according to the IEC 60068-2-48
IEC 60068-2-2
IEC 60068-2-1
IEC 60068-2-30
According to the IEC 60255-22-1
2.5 kV
1.0 kV
According to the IEC 6100-4-2 and
IEC 60255-22-2
8 kV
Not applicable
SPA-ZC 402
1MRS755479
35
A040027b
Weight [g]
510