Heat-N-Glo SL-36 Installer's Manual page 35

Fireplace
Hide thumbs Also See for SL-36:
Table of Contents

Advertisement

1. Attach the flashing
and apply sealant
around the edges of
the flashing base.
2. Attach the storm
collar over the flash-
ing joint and apply
sealant between the
storm collar and
vertical pipe.
To seal the roof hole, and to divert rain and snow
from the vent system:
• Attach a flashing to the roof using nails, and use
a non-hardening mastic around the edges of the
flashing base where it meets the roof.
• Attach a storm collar over the flashing joint to
form a water-tight seal. Place non-hardening
mastic around the joint, between the storm collar
and the vertical pipe.
• Slide the termination cap over the end of the vent
pipe and rotate the pipe clockwise 1/4 turn.
TERMINATION
CAP
Roof Pitch
flat to 6/12
6/12 to 7/12
over 7/12 to 8/12
over 8/12 to 9/12
over 9/12 to 10/12
over 10/12 to 11/12
over 11/12 to 12/12
over 12/12 to 14/12
over 14/12 to 16/12
over 16/12 to 18/12
over 18/12 to 20/12
over 20/12 to 21/12
Figure 29. Minimum Height from Roof to Lowest
Discharge Opening
H (min.) ft.
1.0
1.25
1.5
2.0
2.5
3.25
4.0
5.0
6.0
7.0
7.5
8.0
32