Section 3: Installing The Fireplace; Step 1 Locating The Fireplace - Heat-N-Glo SL-36 Installer's Manual

Fireplace
Hide thumbs Also See for SL-36:
Table of Contents

Advertisement

Step 1
Locating the
Fireplace
Clearance Requirements
The top, back, and sides of the fireplace are defined by stand-offs.
Minimum Clearances from the Fireplace to
Glass
Front
Floor
36 inches
0
(914 mm)
The minimum clearance to a perpendicular wall extending past the face of
the fireplace is one inch (25 mm).
The back of the SL-32 Series fireplaces may be recessed 16 1/4 inches
(413 mm) into combustible construction.
The back of the SL-36 Series fireplaces may be recessed 15 3/4 inches
(400 mm) into combustible construction.
The diagram below shows space and clearance
requirements for locating a fireplace within a room.
Figure 6.
Fireplace Dimensions, Locations,
and Space Requirements
Combustible Materials
Back of
Sides of
Fireplace
Fireplace
1/2 inch
1/2 inch
(13 mm)
(13 mm)
Top of
Fireplace
Ceiling
3-1/2 inches
31 inches
(89 mm)
(787 mm)
3
Installing the
Fireplace
10