36
Mantel Requirements
•
Use the table below to determine the maximum mantel depth allowed. The mantel depth (measured
from the non-combustible facing) must fall within the shaded portion of the table.
•
Any material above the fireplace that protrudes more than 3/4" (19mm) from the non-combustible
facing is considered a mantel and must meet the mantel requirements.
53-3/4" (1365mm)
52-3/4" (1340mm)
51-3/4" (1314mm)
Mantel
50-3/4" (1289mm)
Height
49-3/4" (1264mm)
Above
48-3/4" (1238mm)
47-3/4" (1213mm)
Base (a)
46-3/4" (1187mm)
45-3/4" (1213mm)
44-3/4" (1213mm)
43-3/4" (1213mm)
Mantel Columns
© Travis Industries
Installation
(for qualified installers only)
Maximum Mantel Depth (b)
b
a
Combustible mantel columns (legs) that protrude more than 3/4" (19mm) from the
glass frame must meet the 5" (127mm) sidewall clearance . If they protrude 3/4"
(19mm) or less, they must meet the facing clearance, 2-1/4" (57mm) from the glass
frame - to the side of the fireplace, not in front of it.
Non-combustible mantel columns do not have a minimum clearance.
4100728
100-01254_000