Gree GA Series Product Data page 33

Packaged terminal air conditioner / heat pump 7,000-15,000 btuh
Table of Contents

Advertisement

PERFORMANCE AND ELECTRICAL DATA (CONT.)
APPLICATION CONSIDERATIONS
Installation instructions are shipped with all PTAC
units. It is important that air conditioning systems be
HEAT PUMP MODELS
properly sized and installed for each application in
order to achieve the desired temperature and humidity
levels within the space to be conditioned. It is
MODEL NUMBER
strongly recommended that a professional engineer
Cooling
Btuh
match the PTAC units with the building structure and
climate.
PTAC-GAA07AB-D
7600/7700
The following application considerations are all
important in choosing the proper PTAC system for
PTAC-GAA09AB-D
8800/9000
the building structure.
PTAC-GAA12AB-D
11800/12000
Undersizing
PTAC-GAA15AB-D
15000
If a PTAC unit is undersized (cooling capacity is less
than required load for an application), the unit
POWER
MODEL
will not be able to cool the space down to the desired
FACTOR
NUMBER
(%)
temperature during very hot days. The result could be
warm and humid or warm and dry conditioned space.
PTAC-GAA07AB-D
97%
Oversizing
PTAC-GAA09AB-D
99%
If a PTAC unit is oversized (cooling capacity is
PTAC-GAA12AB-D
99%
greater than required load for the specific application),
the unit will cool the space down to the desired
PTAC-GAA15AB-D
98%
desired temperature too quickly.
LEGEND
EER — Energy Efficiency Ratio
The unit will cycle on and off, however,
* Rated in accordance with ARI Standard 380-93.
† See power cord selection guide below for electric heating capacity rating. Using 30 Amp cords on U07 and U09 models could result in damage to unit.
dehumidification only takes place when the unit is
Fan motor indoor CFM (LO/HI) shown for 230-1-60 units.
operating. The result of this type of application in a
POWER CORD SELECTION GUIDE
hot and/or humid climate would be a cool, yet
GA PTACs are not individually equipped with a power cord, so one must be ordered separately based on the voltage and
excessively humid, space.
amperage of your electrical circuit. If the unit is to be plugged into a receptacle, then a line cord connection kit needs to be
selected. If it will be permanently connected, a hardwire connection must be used.
Air Infiltration
Excessive air infiltration can intensify problems
Model No.
Voltage
associated with undersizing or oversizing a PTAC
PWRCORD ---230V ---15A
unit. This can be the cause of insufficient cooling,
208/230V
PWRCORD ---230V ---20A
dehumidification, or heating. Sources of air
PWRCORD ---230V ---30A
infiltration include vents, gaps around windows and
doors, and improperly sealed floors, ceilings or wall
RECEPTACLE AND FUSE TYPES
joints.
UNIT NAMEPLATE VOLTAGE
OUTLET RATED VOLTS/AMPS
OUTLET BLADE CONFIGURATION
RECEPTACLE TYPE
NEMA CONFIGURATION
TIME DELAY FUSE OR CIRCUIT BREAKER (AMPS)
NOMINAL HEATER SIZE
LEGEND
National Electrical Manufacturers Association
NEMA ---
* May be used for 15 ---amp applications if fused for 15 amps.
MODEL PTAC-GAA (208/230-1-60)
CAPACITY*
Heating
Rev.Cyc.
Electric†
BtuH
6100/6300
15 or 20 Amp
cord only
7900/8100
10500/10700
15, 20 or 30
Amp cord
13800
FAN MOTOR
Indoor
Outdoor
Indoor
Motor Full
Motor
Motor HP‡
Load Amps
HP
0.024
0.1
0.054
0.029
0.2
0.054
0.031
0.2
0.088
0.031
0.2
0.088
Receptacle
Heating
Type
(BTUH)
15 amp /250
5500/6800
20 amp /250
8300/10200
30 amp /250
13900/17000
250/15
A
6--- 15R
15
1.6/2.0 KW
Condensate Removal
Gree's GA series has a new condensate (water)
disposal system. The outdoor fan prop has a built in
slinger ring which draws condensate water through a
suction port built into the outdoor coil shroud. The
VOLTAGE
EER
COP‡
RANGE
water passes though the suction port and is sprayed
on the warm outdoor coil for evaporation. Thus
providing better disposal of excess condensate and
12.2/12
3.4/3.4
improving unit operating efficiency.
11.4/11.3
3.3/3.3
187 - 253
It is normal and desirable to have some condensate
10.5/10.7
3.1/3.1
water in the ebase pan to boost operating efficiency.
9.8
2.9
207-253
NOTE: This unit will not always evaporate 100%
of the unit generated condensate and blown in
rain water. If it is necessary to control 100% of
R-410a
the condensate, the Drain Kit (Part No.: DRAIN-
Outdoor
CHARGE
KIT-4PK) and a building condensate drain
oz
Motor Full
Load Amps
system is recommended.
0.35
23.6
0.35
33.5
0.6
35.3
0.6
38.1
Input Power
Heater (Kw)
(WH)
1.6/2.0
1643/2047
2.5/3.0
2496/3036
4.1/5.0
4118/5037
208/230
250/20
B
6--- 20R
20*
2.5/3.0 KW
33
5
COOLING
AMPS
WATTS
3.0/2.8
620/640
3.9/3.7
770/800
5.3/5.1
1120/1120
6.7
1530
APPROX.
MAX
SENSIBLE
CHASSIS
DEHUM.
HEAT
SHIP WT.
Pint/Hr
FACTOR
lb
1.7
84%
121
2.2
81%
128
2.7
67%
137
3.2
65%
143
Branch
Current
Circuit Full
(Amps)
Amps
7.9/8.9
15
12.2/13.2
20
20.5/21.5
30
250/30
C
6--- 30R
30
4.1/5.0 KW