Lamp Test

conditions on the FACP have changed since the last panel activation. Table 5-1 lists possible panel activations and
the LEDs which will be on for each in Last Event/History Mode.
History Mode
TABLE 5-1:
Latest Panel Activation
AC Power Loss or Brownout
Notification Appliance Circuits Silenced by Silence Switch
Remote Annunciator Trouble
Notification Appliance Circuit Fault
Reverse Polarity Module
To return the control panel to Normal Mode, remove the Security Key from connector J4 on the MS-2410BC main
circuit board. Remove the programming keys function label and reinsert the Normal Mode label C.
The control panel will automatically revert back to Normal Mode after 2 minutes in Last Event/History Mode. If the
Security Key is still installed, the panel keypad will function as expected in Normal Mode. To enter any other mode
of operation, the Security Key must be removed and then reinserted.
5.3
Lamp Test
To perform a Lamp Test, press and hold the Reset/Lamp Test key for more than two seconds. All panel LEDs will
turn on and the piezo sounder will activate.
50
Zone Alarm
Zone Supervisory
Zone Trouble
Ground Fault
Zone Disabled
Zone Alarm LED & System Alarm LED
Zone Supervisory LED & System Supervisory LED
Zone Trouble LED & System Trouble LED
Zone Trouble LED & Zone Disabled LED
Annunciator Trouble LED
NAC Fault LED & System Trouble LED
System Trouble LED
Document #50801
Rev.B
8/17/98
P/N 50801:B
LEDs Illuminated
AC Power LED
Signal Silence LED
Ground Fault LED