Controls and Indicators

Nonresettable 24 VDC Power - TB2 Terminals 1(-) & 2(+)
Maximum ripple voltage: 10 mV
Total DC current available from this output is up to 500 mA
Recommended maximum Standby current is 150 mA
Refer to Fire•Lite Device Compatibility Chart for compatible listed devices
Remote Trouble Buzzer - TB5
Operating Voltage: nominal 24 VDC
DC current when RTB Remote Trouble Buzzer is in normal standby (AC Power LED on alone) is 20 mA.
Maximum DC current from this output when RTB Remote Trouble Buzzer is active is 50 mA.
1.3
Controls and Indicators
Front Panel Membrane Keys in Normal Mode
Acknowledge
Signal Silence
Drill
Disable/Enable
Reset/Lamp Test
Note that programming keys function slide-in-labels and
option/feature slide-in labels are also provided and should
be inserted while in Program Mode to view the altered key
functions. Refer to Figure 3-1, "Programming Mode Key-
pad," on page 30 and "Slide-in Labels" on page 55.
LEDs
AC Power - green LED
Alarm - red LED
Trouble - yellow LED
Supervisory - yellow LED
Signal Silence - yellow LED
NAC Fault - yellow LED
Ground Fault - yellow LED
Battery Trouble - yellow LED
Zone Disabled - yellow LED
Annunciator Trouble - yellow LED
Zone Fire Alarm - Zones 1 through 10 - red LEDs
Zone Supervisory Alarm - Zones 9 and 10 only - red LEDs (yellow LEDs for Canadian program option)
Zone Trouble - Zones 1 through 10 - yellow LEDs
Note: A blank slide-in label is provided for circuits 1 through 10 which may be customized by the customer. In
addition, slide-in-labels listing the programming features/options and programming key functions are provided and
should be inserted while in Program Mode.
1. Total current for nonresettable power, four-wire smoke power, and two Notification Appliance Circuits must not exceed 6.0
amps. Total system current in excess of 3.6 amps requires the XRM-24 Transformer and 12 Amp Hour or 18 Amp Hour
batteries.
10
Operating Voltage nominal 24 volts
RMS
FIGURE 1-3:
Document #50801
1
LEDs and Keypad
Rev.B
8/17/98
P/N 50801:B