5.12 Event Descriptions (Alarms)
There are 6 alarm groups which upon activation will be displayed at the end
of the opening menu. These are:
INPUT:
BATTERY:
OUTPUT:
ENVIRONMENTAL:
SERVICE1:
SERVICE2:
The following lists the mnemonics and description for each alarm group:
INPUT:
FREQ_LO
FREQ_HI
GLITCH
SPIKE
SAG
SURGE
BROWNOUT
SLOW_SURGE
BLACKOUT
BATTERY:
LO_BAT_SHTDWN - battery voltage shutdown level detected
LO_BAT_WARN
BAT_VOLT_HI
FAIL_SELF_TEST - failed self test *
BATT_FLT
OUTPUT:
VOLT_LO
VOLT_HI
PWR_OVLD
VA_OVLD
OVER_V_FLT
SHORT_CCT
ENVIRONMENTAL:
AMB_TEMP_HI
SERVICE 1:
SERV CODE 1
SERVICE 2:
SERV CODE 2
SERV CODE 3
SERV CODE 4
SERV CODE 5
SERV CODE 6
EMGNCY POFF
OUTV SHTDWN
*(service light alarm)
5. RS-232 TERMINAL COMMUNICATION
- input line frequency low
- input line frequency high
- input line glitch has been detected
- input line spike has been detected
- input line sag has been detected
- input line surge has been detected
- input line brownout has been detected
- input line slow surge has been detected
- input line blackout has been detected
- battery voltage low warning level detected
- battery over voltage level detected *
- battery fault has been detected *
- output voltage low has been detected
- output voltage high has been detected
- output power overload has been detected
- output VA overload has been detected
- output over voltage fault has been detected *
- output short circuit has been detected *
- high internal ambient temperature detected *
- phase lock loop failure has been detected *
- micro software reset has been activated
- micro hardware reset has been activated
- power board EEPROM fault has been detected *
- power board hardware fault has been detected *
- neg DC supply rail has been detected *
- emergency power off has been activated
- remote shutdown feature is currently active
43